TITLE community-development

Part I. Texas Department of Housing and Community Affairs

Chapter 80. Manufacctured Housing

Subchapter D. Standards and Requirements

10 TAC §§80.53-80.55

The Texas Department of Housing and Community Affairs ("TDHCA") adopts amendments to the Manufactured Housing Rules, 10 Texas Administrative Code, §§80.53-80.55 relating to the installation of manufactured homes. Section 80.53 relating to manufacturer's design requirements is adopted without changes and will not be republished. Section 80.54 and §80.55, relating to installation standards and anchoring systems for manufactured homes are adopted with changes to the proposed text as published in the May 7, 1999, issue of the Texas Register (24 TexReg 3432).

Only a structural change was made to §80.54(b)(5) (Paragraph (5) was broken down into subparagraph (A) and (B)). Two words "after moistening" were added to paragraph (4) in §80.55(d). The changed sections are being republished.

A public hearing was held on Tuesday, June 8, 1999. There were no comments presented by groups or associations.

All comments, both oral and written are discussed together infra. Following a summary of the comments is a statement of the reasons why the department agrees or disagrees with the party submissions or proposals.

COMMENTS ON SPECIFIC SECTIONS OF THE RULES:

The following comments were received regarding the proposed rules and are as follows:

COMMENT REGARDING §80.53(e): One commenter wants to change the sentence concerning printed instructions provided with each home and require two copies of the printed instructions to be provided with each home.

TDHCA does not agree. Even though this is a good suggestion, this sentence in the present rules was not proposed for amendment and is similar to 24 CFR 3280.306(b)(1) of the Federal Manufactured Home Constructions and Safety Standards. Home manufacturers might object to this suggested new requirement and cite Section 604(d) of the National Manufactured Housing Construction and Safety Standards Act, which prohibits states from adopting different standards.

COMMENT REGARDING §§80.53(e) & 80.55(d)(4): One commenter asked that the Department provide references to soil class and torque values concerning rock anchors in mixed soil and rock or in hard caliche soil. The proposed rule has the following clause, "When approved auger anchors cannot be inserted into a difficult soil, such as mixed soil and rock or caliche (heavily weathered limestone) that is not solid rock, . . ." the commenter believes that installers might misinterpret the proposed rule and incorrectly use cross drive rock anchors in dry clay soil types that are affected by moistening. The commenter recommends that the proposed rule describe the minimum soil test probe torque value for a difficult soil. Also the commenter recommends that the proposed rule express that the alternative use of cross drive rock anchors is not for soils that can be penetrated by auger anchors after moistening.

TDHCA does not completely agree. The department's Manufactured Housing Anchor Installation Task Force reviewed a report about cross drive rock anchors tested in Kerrville. The substantiating anchor pull out tests conducted in Kerrville concerned the alternative use of cross drive rock anchors in soil and rock mixtures that cannot be penetrated by auger anchors after moistening. The Department does not agree that the minimum soil test probe torque value for a difficult soil should be described in the proposed rule. For difficult soils, rock fragments often resist the soil test probe penetration. A high soil test probe torque measurement may also indicate a dry clay that is affected by moistening. The Department does agree that the proposed rule must express that difficult soils are soils that are not affected by moistening. Therefore, the Department proposes to add the words "after moistening" as follows in proposed §80.55(d)(4), "When approved auger anchors cannot be inserted into a difficult soil after moistening, such as mixed soil and rock or caliche (heavily weathered limestone) that is not solid rock, . . ."

COMMENT REGARDING §80.54(a)(2): One commenter does not agree with giving the manufacturer the option of modifying the state's generic standards with an appendix. The commenter believes that a copy of the home manufacturer's appendix to the generic standards will not be provided to the installer.

TDHCA does not agree. Present rule §80.51(a)(3) requires the home manufacturer to mail a copy to the retailer. For new homes, the retailer is responsible for the installation.

COMMENT REGARDING §§80.54(b)(4)(1) & (c): One commenter believes that in areas where footings are not to be located, all debris, sod, tree stumps and other organic material shall be completely removed. The present rule allows this material to be trimmed, cut, or removed down to a maximum height of 8 inches above the ground. The proposed rule deletes the phrase "or to a lower level if needed to properly install the vapor retarder material.

TDHCA does not agree with the suggested change. In order to save consumer site preparation costs, the proposed rule describes the minimum amount of organic material removal.

COMMENT REGARDING §80.54(b)(2) & (5): One commenter believes the cost estimates for the vapor retarder are too low.

TDHCA does not agree. During the June 24, 1998 Public Hearing, the Texas Manufactured Housing Association testified that they were informed that the cost was about $100 per section. At this time, the Department does not have any other evidence about costs for materials and labor for the ground vapor retarder.

COMMENT REGARDING §80.54(b)(2) & (5): One commenter believes the proposed rule must be clarified concerning installer responsibility for the skirting ventilation. The commenter said some of the requirements in the generic standards, relating to the installation of a vapor retarder, appear to pertain to the skirting installer - not the manufactured housing installer.

TDHCA does not agree that the rule must be clarified. If the retailer or installer provides the materials for skirting or contracts for the installation of skirting, the retailer or installer is responsible for installing any required moisture and ground vapor control measures in accordance with the home installation instruction or the generic standards and for providing for the proper cross ventilation of the crawl space. For new manufactured homes, the retailer is the contracting installer. Rule 24 CFR 3282.252(b) of the Federal Manufactured Homes Procedural and Enforcement Regulations states, "A sales transaction with a purchaser is considered completed when all the goods and services that the dealer agreed to provide at the time the contract was entered into have been provided." The Texas Manufactured Housing Standards Act, Section 6(c) states, "It is unlawful for any manufacturer, retailer, broker, installer, or lienholder to make any alteration, repair, or replacement of any component or systems in and to a used manufactured home which will result in making the home not habitable."

COMMENT REGARDING §80.54(b)(4): One commenter believes that the phrase "strongly recommended that the installer not install the home unless exterior grade is sloped away from the home" is not defined enough.

TDHCA does not agree to change the phrase and make the installer responsible for the grading of the home site. The Citizen's Advisory Commission on Manufactured Housing Rules reached a consensus on the present wording. There was no consensus to require installers to grade the home site.

COMMENT REGARDING §80.54(b)(5): One commenter recommends additional field testing of vapor retarders before adopting the proposed rule.

TDHCA does not agree. The Department believes that there is no need to conduct additional field testing about a nationally recognized standard. An American National Standard, Manufactured Home Installations, NCSBCS/ANSI A225.1-1994, Section 3.5.1 states, "If the space under the home is to be enclosed with skirting or other material, a vapor retarder that keeps ground moisture out of the home shall be installed."

COMMENT REGARDING §80.55: One commenter said the rock anchor rules are contradictory to some of the rules currently in effect. The commenter believes the proposed rule contradicts another rule that does not allow two anchors to be within 48 inches of each other. Table 4(a) explains how far apart to set piers and anchors. However; in some cases, doubling the rock anchors is going to put these anchors closer than the four foot minimum requirement. The Wind Zone II homes may have 15 vertical ties per side and the proposed rules state that all ties must be attached. If the second installation is done in rocky soil conditions and rock anchors are attached, vertical ties are not supposed to be attached to rock anchors. The commenter said they will be violating the rules whether they attach the ties or not.

TDHCA does not agree. For twelve foot wide home sections with floor joists more than 41 inches above the anchor head, Table 4A specifies the spacing for diagonal ties to be seven feet or less. The alternative use of cross drive rock anchors is not allowed, since seven feet divided by 2 gives a spacing of 3.5 feet. Note 9 of Table 4A states that no two anchors shall be within 48 inches of each other. The proposed rule does not contradict Table 4A. In practical terms, the proposed rule limits the vertical distance between an anchor head and the floor joists. The Department's Manufactured Housing Anchor Installation Task Force did not receive any pull out test evidence for the alternative use of cross drive rock anchors with spacings less than four feet apart.

COMMENT REGARDING §80.55: One commenter believes that the proposed rule does not provide a moderate cost anchoring method for installing homes with built-in vertical ties.

TDHCA agrees that a home designed for Wind Zone II, with many built-in vertical ties, will cost more to anchor in Wind Zone I in accordance with the proposed generic standard than a home designed for Wind Zone I. However, the installer has the option to follow a custom designed anchoring system which specifies the minimum number of vertical ties for the lower wind pressures. The Department's Manufactured Housing Anchor Installation Task Force did not receive any pull out test evidence for the alternative use of cross drive rock anchors in difficult soils with vertical tie loads. No change was made as a result of the comment.

This is the end of comments.

The following is a restatement of the rules' factual bases:

TDHCA recommends changes to rules §§80.53 - 80.55, regulating installation of manufactured housing. The following describes the reasons for the rules.

§80.53(e) is amended to communicate that installers may install cross drive rock anchors in accordance with the generic installation standards.

§80.54(a)(2) is amended so that the generic standards may be modified by an appendix filed in accordance with §80.51(a)(2). If the design of a home requires a change in the generic standards to protect the structural integrity of the home, the home manufacturer may file an appendix to the state's generic standards as part of the home manufacturer's installation instructions.

§80.54(b) is amended to delete the requirement to install a ground vapor barrier material under every manufactured home installed. Retailers or installers are only required to install the ground vapor barrier material if the home is installed per the department's generic standards or if the manufacturer's installation instructions require the material to be installed.

§80.54(b)(3) is amended to explain the standards for ground clearance requirement if a home is installed per the generic standards. If a home is installed in accordance with the home installation instructions, the installer must follow the ground clearance requirement of the home installation instructions.

§80.54(b)(5) is amended to explain the standards for moisture and ground vapor controls and the generic requirement for access openings, since these are measures for monitoring moisture and ground vapor controls. If the space underneath the home is to be enclosed, the retailer and/or installer must notify the purchaser that moisture and ground vapor control measures are required. If a home is installed in accordance with the home installation instructions, the installer must follow the moisture and ground vapor control requirements of the home installation instructions. For the purpose of safety and durability, installers are required to pass the clothes dryer exhaust duct, air conditioning condensation drain, or combustion air inlet through the skirting to the outside, if those items are present.

§80.54(c), the Site Preparation Notice is amended to explain that if skirting is provided, the consumer must be notified that moisture and ground vapor control measures are required. The phrase "ground vapor retarder" was updated to "ground vapor control measures." These changes are required since home installation instructions may require moisture and ground vapor control measures other than a vapor retarder on the ground.

Figure: 10 TAC §80.55(d)(1) and Figure: 10 TAC §80.55(d)(2) are amended to add references to refer to §80.55(d)(4) concerning alternative generic cross drive rock anchor installation instructions.

New §80.55(d)(4) is added because there are presently no cross drive rock anchors or soil auger anchors individually designed and department approved for mixed soil and rock conditions or hard caliche soil. The department has approved particular auger anchor models for installation in soil and particular rock anchor models for installation in solid rock. For difficult soils, the department approved an anchor model with three parallel drive rods and a system including an anchor model with three diverging drive rods. A cross drive rock anchor is a general type of rock anchor with two rods in a crisscross pattern. The Kerrville tests substantiated the alternative use of cross drive rock anchors in soils similar to the soils encountered in Kerrville, if the number of cross drive rock anchors is doubled.

Custom-designed anchor systems or concrete slabs with embedded anchors, are economically prohibitive for most consumers and homeowners who live in areas of difficult soils.

The department found that there was an immediate need for safe, affordable anchoring of new and used manufactured homes in difficult soils, without which there is an imminent peril to occupants and neighboring homes if such anchoring systems are not implemented.

Based upon information provided by license holders and the public, the wording in the expired emergency rule for doubling the amount of cross drive rock anchors and diagonal frame ties should be permanently adopted. Even though two other drive rod anchor models are now approved, installers need an additional method for anchoring homes with cross drive rock anchors until more devices and systems are invented and approved for use in many types of difficult soils with many types of manufactured homes.

The amended sections are adopted under the authority of the Texas Manufactured Housing Standards Act, Article 5221f, §9, which provides the department with authority to amend, add, and repeal rules governing the Manufactured Housing Division of the department.

No other statute, code, or article is affected by the amended rules.

§80.54.Standards for the Installation of Manufactured Homes.

(a)

All manufactured homes shall be installed in accordance with one of the following:

(1)

the home manufacturer's installation instructions;

(2)

the state's generic standards set forth in this section, §80.55 of this title (relating to Anchoring Systems), §80.56 of this title (relating to Multi-Section Connection Standards), and modified by any appendix filed in accordance with §80.51(a)(2) of this title (relating to Manufactured Home Installation Requirements);

(3)

a custom designed stabilization system;

(4)

a stabilization system pre-approved by the department; or

(5)

on a permanent foundation.

(b)

Site Preparation Responsibilities and Requirements:

(1)

The purchaser is responsible for the proper preparation of the site where the manufactured home (new or used) is to be installed unless the home is installed in a rental community. Except in rental communities, the purchaser shall remove all debris, sod, tree stumps and other organic materials from all areas where footings are to be located. In areas where footings are not to be located, all debris, sod, tree stumps and other organic material shall be trimmed, cut, or removed down to a maximum height of 8 inches above the ground. The retailer must give the purchaser a site preparation notice as described in this section prior to the execution of any binding sales agreement. If the installation is a secondary move, not involving a retail sale, the installer must give the homeowner the site preparation notice prior to any agreement for the secondary installation of the home.

(2)

If the retailer or installer provides the materials for skirting or contracts for the installation of skirting, the retailer or installer is responsible for installing any required moisture and ground vapor control measures in accordance with the home installation instructions or the generic standards and for providing for the proper cross ventilation of the crawl space. If the purchaser or homeowner contracts with a person other than the retailer or installer for the skirting, the purchaser or homeowner is responsible for installing the moisture and ground vapor control measures and for providing for the proper cross ventilation of the crawl space.

(3)

Clearance: If the manufactured home is installed according to the state's generic standards, a minimum clearance of 18 inches between the ground and the bottom of the floor joists must be maintained. In addition, the installer shall be responsible for installing the home with sufficient clearance between the I-Beams and the ground so that after the crossover duct prescribed by the manufacturer is properly installed it will not be in contact with the ground. Refer to §80.56 of this title (relating to Multi-Section Connection Standards) for additional requirements for utility connections. It is strongly recommended that the installer not install the home unless all debris, sod, tree stumps and other organic materials are removed from all areas where footings are to be located.

(4)

Drainage: Except in rental communities, proper drainage is the responsibility of the homeowner. It is strongly recommended that the installer not install the home unless the exterior grade is sloped away from the home or another approved method to prohibit surface runoff from draining under the home is provided. Drainage prevents water build-up under the home. Water build-up may cause shifting or settling of the foundation, dampness in the home, damage to siding and bottom board, buckling of walls and floors, delamination of floor decking and problems with the operation of windows and doors.

(5)

Generic Moisture and Ground Vapor Controls:

(A)

If the manufactured home is installed according to the state's generic standards and the space under the home is to be enclosed with skirting and/or other materials provided by the retailer and/or installer, an access opening not less than 18 inches in any dimension and not less than three square feet in area shall be provided by the installer. The access opening shall be located so that any water supply and sewer drain connections located under the home are accessible for inspections. If a clothes dryer exhaust duct, air conditioning condensation drain, or combustion air inlet is present, the installer must pass it through the skirting to the outside. In addition, crawl space ventilation must be provided at the rate of minimum 1 square foot of net free area, for every 150 square feet of floor area. At least six openings shall be provided, one at each end of the home and two on each side of the home. The openings shall be screened or otherwise covered to prevent entrance of rodents (note: screening will reduce net free area). For example, a 16'x76' single section home has 1216 square feet of floor area. This 1216 square feet divided by 150 equals 8.1 square feet or 1166 square inches of net free area crawl space ventilation.

(B)

The retailer and/or installer must notify the purchaser that moisture and ground vapor control measures are required if the space under the home is to be enclosed. Water vapor build-up may cause dampness in the home, damage to siding and bottom board, buckling of walls and floors, delamination of floor decking and problems with the operation of windows and doors. The generic ground vapor control measure shall consist of a ground vapor retarder that is minimum 6 mil polyethylene sheeting or its equivalent, installed so that the area under the home is covered with sheeting and overlapped approximately 12 inches at all joints. Any tear larger than 18 inches long or wide must be taped using a material appropriate for the sheeting used. The laps should be weighted down to prevent movement. Any small tears and/or voids around construction (footings, anchor heads, etc.) are acceptable.

(c)

Notice: The site preparation notice to be given to the consumer shall be as follows:

Figure: 10 TAC §80.54(c)

(d)

Footers and Piers:

(1)

Proper sizing of footings depends on the load carrying capacity of both the piers and the soil. To determine the load bearing capacity of the soil, the installer may use any of the following methods:

(A)

Pocket penetrometer:

(i)

Test a typical area adjacent to or within 10 feet of the perimeter of the unit;

(ii)

Dig down to undisturbed soil. This should be a minimum of 1 square foot surface area; and

(iii)

Using the pocket penetrometer take seven readings, eliminate the highest and the lowest and average the remaining five.

(B)

Soil surveys from the U.S. Department of Agriculture;

(C)

Values from tables of allowable or presumptive bearing capacities given in local building codes. Such tables are commonly available from the local authority having jurisdiction; or

(D)

Any other test data from soil analysis reports.

(2)

The footing must be placed on firm, undisturbed soil, or fill compacted to at least 90% of its maximum relative density. Installation on loose, noncompacted fill may invalidate the home's limited warranty.

(3)

Footer configurations:

Figure: 10 TAC §80.54(d)(3)

(4)

Footer sizing and capacities: The following tables represent maximum loads and spacings based on footer size and soil bearing capacity. Other approved footers may be used if equal or greater in bearing area than those footer sizes tabulated.

Figure: 10 TAC §80.54(d)(4)

(5)

Piers and pier spacings: One of the most important parts of home installation is proper pier installation. Incorrect size, location or spacing of piers may cause serious structural damage to the home. Spacing and location of piers shall be in accordance with the tables listed in these standards (Table 3B, without perimeter piers; Table 3C, with perimeter piers).

(A)

Spacing shall be as even as practicable along each main I-Beam. Pier spacing may exceed tabulated values up to 30% so long as the total pier count remains the same. End piers are to be located within 24 inches of the end of the main frame.

(B)

Piers shall extend at least 6 inches from the centerline of the I-Beam or be designed to prevent dislodgment due to horizontal movement of less than 4 inches.

(C)

Load bearing supports or devices shall be listed by an independent testing laboratory, nationally recognized inspection agency, or other nationally recognized organization and approved by the department. Engineers or architects licensed in Texas may design load bearing supports or devices for a single installation. A copy of the design for this particular home and site shall be provided to the department before the home is installed, but department approval is not required.

(D)

Sidewall openings greater than 4 feet shall have perimeter piers located under each side of the opening, i.e. patio doors, recessed porches/entries, bay windows and porch posts. Perimeter piers for openings are not required for endwalls.

(6)

Pier design: Piers shall be constructed per the following details:

Figure: 10 TAC §80.54(d)(6)

(A)

Shimming (if needed): Hardwood shims are commonly used as a means for leveling the home and filling any voids left between the bottom flange of the I-Beam and the top of the pier cap. Wedge shaped shims must be installed from both sides of the I-Beam to provide a level bearing surface. The allowable height must not exceed 1 inch. Shims shall be at least 4 inches wide (nominal) and 6 inches long. Over shimming should be avoided.

(B)

Table 3B - Pier loads (pounds) at tabulated spacings WITHOUT perimeter supports:

Figure: 10 TAC §80.54(d)(6)(B)

(C)

Table 3C - Pier loads (pounds) at tabulated spacings WITH perimeter supports:

Figure: 10 TAC §80.54(d)(6)(C)

(7)

Typical multi-section pier layout:

Figure: 10 TAC §80.54(d)(7)

(8)

Typical single section pier layout:

Figure: 10 TAC §80.54(d)(8)

(9)

Multi-section units mating line column supports:

(A)

On multi-section units, openings larger than 4 feet must have piers installed at each end of the opening. To determine the pier loads, refer to Table 3D in subparagraph (D) of this paragraph.

Figure: 10 TAC §80.54(d)(9)(A)

(B)

Column loads for each section may be combined when the columns are opposite each other. The footer must be sized for the combined loading.

(C)

Additional piers are required under marriage walls (see wall between column #3 and #4 in the Marriage Line Elevation drawing in subparagraph (A) of this paragraph). The maximum spacing is the same as the spacing at the main I-Beams, without perimeter piers, and one half the spacing of the perimeter piers, with perimeter piers installed.

(D)

Table 3D: Mating line column loads (pounds).

Figure: 10 TAC §80.54(d)(9)(D)

§80.55.Anchoring Systems.

(a)

General Requirements: For units built on or after September 1, 1997, the installer must verify that the unit is designed for the Wind Zone in which it is to be installed. Note: A Wind Zone I unit, built on or after September 1, 1997, may not be installed in a Wind Zone II area. However, a Wind Zone II unit may be installed in a Wind Zone I area.

Figure: 10 TAC §80.55(a)

(b)

Material Specifications:

(1)

Strapping shall be Type 1, Finish B, Grade 1 steel strapping, 1­1/4 inches wide and 0.035 inches in thickness, certified by a licensed professional engineer or architect as conforming with the American Society for Testing and Materials (ASTM) Standard Specification D3953 91, Standard Specification for Strapping, Flat Steel, and Seals. Tie materials shall be capable of resisting an allowable working load of 3,150 pounds with no more than 2% elongating and shall withstand a 50% overload (4,725 pounds total). Ties shall have a resistance to weather deterioration at least equivalent to that provided by coating of zinc on steel of not less than 0.30 ounces per square foot on each side of the surface coated (0.0005 inches thick), as determined by ASTM Standards Methods of Test for Weight of Coating on Zinc-coated (galvanized) Iron or Steel Articles (ASTM A 90-81). Slit or cut edges of zinc-coated steel strapping are not required to be zinc coated.

(2)

All anchoring components must be approved by the department. Installers shall only use approved anchoring components. An installer may obtain a list of approved anchoring components from the department, anchor manufacturer and/or supplier of anchoring components.

(c)

Anchors shall be installed per the following details:

(1)

in direction of load,

Figure: 10 TAC §80.55(c)(1)

(2)

installed against direction of load (vertical and/or angled), a stabilizer plate must be installed.

Figure: 10 TAC §80.55(c)(2)

(d)

WIND ZONE I Installation:

(1)

Typical anchor layout, single and multi-section units (WIND ZONE I ONLY):

Figure: 10 TAC §80.55(d)(1)

(2)

Table 4A: The following table describes the maximum spacing for diagonal ties along each side of the unit.

Figure: 10 TAC §80.55(d)(2)

(3)

Table 4B: Minimum number of diagonal ties required per side, per unit length. Table based on 2 feet inset of anchors at each end.

Figure: 10 TAC §80.55(d)(3)

(4)

When approved auger anchors cannot be inserted into a difficult soil after moistening, such as mixed soil and rock or caliche (heavily weathered limestone) that is not solid rock, approved cross drive rock anchors may be used in accordance with the values and notes for Table 4A in paragraph (2) of this subsection modified as follows:

(A)

since the ultimate anchor pull out in the difficult soil will be reduced, the maximum spacing for diagonal ties per side is one half the spacing allowed by Table 4A which will require adding one additional cross drive rock anchor for each anchor specified;

(B)

the rods of the approved cross drive rock anchors must be fully inserted, have at least 24 inches of the rod lengths embedded in the difficult soil, and be restrained from horizontal movement, when feasible, by a stabilizer plate between the rods and the home; and

(C)

each cross drive rock anchor is connected to one diagonal tie and is not connected to a vertical tie.

(e)

WIND ZONE II Installation:

(1)

In place of the requirements as shown in subsection (d) of this section, units designed for Wind Zone I and built prior to September 1, 1997, and units designed for Wind Zone II and built prior to July 13, 1994, require diagonal ties as set forth in Table 5A when these units are installed in Wind Zone II. See also §80.50 of this title (relating to Wind Zone Regulations). Items not specifically addressed in this section are the same as for Wind Zone I installations.

Figure: 10 TAC §80.55(e)(1)

(2)

Units built to Wind Zone II on or after July 13, 1994.

(A)

Units built to Wind Zone II on or after July 13, 1994, should have either built-in, or provisions for connecting, vertical ties along the sidewall(s) of each unit(s). A diagonal tie must be installed at each vertical tie location (except for designated shearwall tie). Built-in vertical ties shall be connected to anchors. If there are brackets or other provisions for connecting vertical ties, vertical ties shall be added at the brackets or provisions and connected to anchors.

(B)

Only factory installed vertical ties may be closer than 4 feet from each other.

(C)

Where tie locations are clearly marked as a shear wall strap, a perimeter pier must be installed at that location. See subsection §80.54(c) of this title (relating to Standards for the Installation of Manufactured Homes) for perimeter pier construction. Diagonal tie is not required.

(D)

Where the vertical tie spacing exceeds 8'-0" on-center (see also note 6 in table 5A for exception), the anchoring system must be approved by the home manufacturer's installation manual, or designed by a professional engineer or architect licensed in the state of Texas.

(E)

Where pier heights exceed 36 inches in height, the diagonal strap shall be connected to the opposite I-Beam (see Figure 1).

Figure: 10 TAC §80.55(e)(2)(E)

(F)

Where vertical tie locations are not easily discernable, the vertical ties may be connected to the main I-Beam rails and the anchor installed directly below that connection point. The diagonal tie must be connected to the opposite main I-Beam. In no case shall the distance between those ties exceed 5'-4" on-center (see Figure 2).

Figure: 10 TAC §80.55(e)(2)(F)

(3)

Multi-section centerline anchoring requirements (Wind Zone II only):

(A)

centerline anchor ties are required for ALL Wind Zone II installations, regardless of the date the unit was manufactured, when installation occurs on or after the effective date of these rules.

(B)

factory installed centerline vertical ties, brackets, buckles or any other connecting devices must be connected to a ground anchor. No additional anchors as described in subparagraph (D) of this paragraph are required.

(C)

to avoid obstructions and/or piers and footers, the anchor may be offset up to 12 inches perpendicular to the centerline.

(D)

where factory preparations do not exist, install anchors and angle iron brackets at each side of mating line openings wider than 48 inches per table 5B (see Figure 5B for detail).

(i)

Where equal spans exist opposite each other (i.e., each section), a double bracket assembly may be used. The maximum opening is per table 5B. Total uplift load may not exceed the anchor and/or strap capacity (i.e., 3150 pounds).

(ii)

the angle iron bracket is minimum 11 gauge. The holes for the lag screws are a maximum of 4 inches apart.

(iii)

lag screws/bolts are minimum 5/16 x 3 inches, full thread.

(4)

For openings separated by a wall or post 16 inches or less in width, the opening span is the total of the spans on each side of the wall/post.

(f)

Bracket Installation.

(1)

Table 5B: Maximum Centerline wall opening for column uplift brackets (see figure 5B for typical installation details).

Figure: 10 TAC §80.55(f)(1)

(2)

Figure 5B shows both single and double bracket assemblies for illustration purposes only. Use a single bracket for openings which exist on one section only. Use double bracket where openings are opposite each other on two sections of the home.

(3)

When only one bracket assembly is required, it may be installed on either side of the column/opening stud(s), but no more than 12 inches from the column or opening stud(s). (See examples in figure 5C.)

(4)

When two bracket assemblies are required, they must be installed on each side of the column/opening stud(s), but no more than 12 inches from the column/opening stud(s) (see examples in figure 5C), and they must be angled away from each other a minimum of 12 inches.

Figure: 10 TAC §80.55(f)(4)

(5)

Example: A double section unit with each section being 14 feet wide;

(A)

Span "A" is 18'-0", matching span both sections;

(B)

Span "B" is 14'-8", matching span both sections;

(C)

Span "C" is 6'-8", matching span both sections; and

(D)

Span "D" is 13'-4", one side only.

Figure: 10 TAC §80.55(f)(5)(D)

(6)

Longitudinal ties:

(A)

Longitudinal ties are required for ALL Wind Zone II installations, regardless of date of manufacture, when installation occurs after the effective date of these rules.

(B)

Longitudinal ties are designed to prevent lateral movement along the length of the home.

(C)

The strap may be connected or wrapped around front or rear chassis header members, around existing chassis cross members, or spring hangers. Their location along the length of the home is not critical, as long as the number of longitudinal ties required for each end of each home section are installed with their pull in opposite directions. See Figures 1 and 2 in subparagraph (D) of this paragraph.

(D)

Units less than 60 feet in box length require at least two longitudinal ties per end per section. These longitudinal ties are in addition to the sidewall ties.

Figure: 10 TAC §80.55(f)(6)(D)

This agency hereby certifies that the adoption has been reviewed by legal counsel and found to be a valid exercise of the agency's legal authority.

Filed with the Office of the Secretary of State on August 3, 1999.

TRD-9904760

Daisy A. Stiner

Executive Director

Texas Department of Housing and Community Affairs

Effective date: October 2, 1999

Proposal publication date: May 7, 1999

For further information, please call: (512) 475-3726