TITLE 10.COMMUNITY DEVELOPMENT

Part 1. TEXAS DEPARTMENT OF HOUSING AND COMMUNITY AFFAIRS

Chapter 80. MANUFACTURED HOUSING

The Manufactured Housing Division of the Texas Department of Housing and Community Affairs (the "Department") proposes new §§80.57 - 80.59, 80.129, 80.240 in new Subchapter H (Tables and Figures) and 80.260 in new Subchapter I (Forms) and amendments to §§80.10, 80.11, 80.20, 80.53 - 80.56, 80.62, 80.64, 80.66, 80.119 - 80.128, 80.130 - 80.133, 80.135, 80.183, and 80.205 for the following purpose: make the rules more useful, practical and as understandable as possible; organize rules by related subjects more logically; eliminate unnecessary or redundant verbiage; and clean up areas of confusion or conflict.

There is an adoption currently pending for §80.201(e) relating to the Issuance of Statements of Ownership and Location, so the additional revisions to this rule cannot be proposed until the pending adoption is effective. Effective date of adoption is 30 days after the adopted rule is published in the Texas Register . The Department will propose the additional revisions for public comment as soon as adoption of §80.201(e) is effective.

Because the Department no longer employs an engineer, the drawings in proposed §80.240(b)(9), (22), and (23) have not been reviewed or approved by a Department engineer.

Section 80.10 is revised to update the rule with the current installation and construction standards.

Section 80.11 - Deleting unnecessary definitions, ones that are addressed in other rules or that exist in the State and Federal statutes, proposing new definitions and revising existing definitions for clarification.

Section 80.20 - Revised for clarification and updating of fees, and relocated fees for Statements of Ownerships and Location from §80.202 to §80.20(j).

Section 80.53 - Changed title of rule and revised for clarification.

Section 80.54 - Revised to organize in a more logical manner and eliminate unnecessary or redundant verbiage. The tables and figures are relocated to new Subchapter H (Tables and Figures).

Figure: 10 TAC §80.54(g) - Moved Site Preparation Notice to §80.260(a)(1).

Figure: 10 TAC §80.54(h)(3) - Moved footer configurations to §80.240(b)(22).

Figure: 10 TAC §80.54(h)(4) - Moved footer capacities table to §80.240(a)(8).

Figure: 10 TAC §80.54(h)(6) - Moved pier design figure to §80.240(b)(23).

Figure: 10 TAC §80.54(h)(6)(B) - Moved pier loads without perimeter supports table to §80.240(a)(9).

Figure: 10 TAC §80.54(h)(6)(C) - Moved pier loads with perimeter supports table to §80.240(a)(10) and moved perimeter pier front and side view figure to §80.240(b)(24).

Figure: 10 TAC §80.54(h)(7) - Moved typical multi-section pier layout figure to §80.240(b)(25).

Figure: 10 TAC §80.54(h)(8) - Moved typical single section pier layout figure to §80.240(b)(26).

Figure: 10 TAC §80.54(h)(9)(A) - Moved determining column load and marriage line elevation figure to §80.240(b)(27).

Figure: 10 TAC §80.54(h)(9)(D) - Moved mating line column loads table to §80.240(a)(11).

Section 80.55 - Revised to organize in a more logical manner and eliminate unnecessary or redundant verbiage. The tables and figures are relocated to new Subchapter H (Tables and Figures).

Figure: 10 TAC §80.55(a) - Moved counties Located in Wind Zone II figure to §80.240(b)(1).

Figure: 10 TAC §80.55(c)(1) - Moved anchor installation figure to §80.240(b)(2).

Figure: 10 TAC §80.55(c)(2) - Moved placement of stabilizing plates figure to §80.240(b)(3).

Figure: 10 TAC §80.55(d)(1) - Moved Wind Zone I Installation figure to §80.240(b)(4).

Figure: 10 TAC §80.55(d)(2) - Moved maximum spacing for diagonal ties table to §80.240(a)(1).

Figure: 10 TAC §80.55(d)(3) - Moved minimum number of diagonal ties table to §80.240(a)(2).

Figure: 10 TAC §80.55(e)(1) - Moved maximum spacing for diagonal ties per side table to §80.240(a)(3).

Figure: 10 TAC §80.55(e)(2)(E) - Moved diagonal strap placement figure to §80.240(b)(5).

Figure: 10 TAC §80.55(e)(2)(F) - Moved diagonal and vertical ties figure to §80.240(b)(6).

Figure: 10 TAC §80.55(f)(1) - Moved maximum centerline wall opening for column uplift brackets table to §80.240(a)(4).

Figure: 10 TAC §80.55(f)(4) - Moved the typical installation details figure to §80.240(b)(7).

Figure: 10 TAC §80.55(f)(5)(D) - Moved the anchor span figure to §80.240(b)(8).

Figure: 10 TAC §80.55(f)(6)(D) - Moved the longitudinal ties figure to §80.240(b)(10).

Section 80.56 - Revised for clarification and to relocate the tables and figures to new Subchapter H (Tables and Figures).

Figure: 10 TAC §80.56(a)(4) - Moved the mating line surfaces figure to §80.240(b)(11).

Figure: 10 TAC §80.56(b)(5) - Moved the floor connections table to §80.240(a)(5) and moved the floor connections figure to §80.240(b)(12).

Figure: 10 TAC §80.56(c)(2) - Moved the endwall connections figure to §80.240(b)(13).

Figure: 10 TAC §80.56(d)(3) - Moved the roof connections table to §80.240(a)(6).

Figure: 10 TAC §80.56(d)(4) - Moved the roof connection figure to §80.240(b)(14).

Figure: 10 TAC §80.56(e)(6) - Moved the exterior roof close up figure to §80.240(b)(15).

Figure: 10 TAC §80.56(g)(4) - Moved the HVAC crossover figure to §80.240(b)(16).

Figure: 10 TAC §80.56(h)(1) - Moved the multi-section water crossover connection figure to §80.240(b)(17).

Figure: 10 TAC §80.56(i)(2)(F) - Moved the Drain, Waste and Vent Floor Piping System figure to §80.240(b)(18).

Figure: 10 TAC §80.56(j)(2) - Moved the chassis bonding figure to §80.240(b)(19).

Figure: 10 TAC §80.56(j)(3) - Moved the electrical crossover figure to §80.240(b)(20).

Figure: 10 TAC §80.56(j)(6) - Moved the main panel box feeder conductor sizes table to §80.240(a)(7).

Figure: 10 TAC §80.56(k)(2) - Moved the fuel gas pipe crossover connections figure to §80.240(b)(21).

New §80.57 - Relocated text previously in §80.54(f) and (g) to organize and group in a more logical manner and moved the tables and figures previously included with the text to new Subchapter H (Tables and Figures).

New §80.58 - Relocated text previously in §80.54(h) to organize and group in a more logical manner and moved the tables and figures previously included with the text to new Subchapter H (Tables and Figures).

New §80.59 - The new rule identifies exceptions to the generic installation standards filed with the department by manufacturers in accordance with §80.53(g).

Section 80.62 - The Department now registers stabilizing components and systems, but no longer approves them. Also, revisions were made for clarification.

Section 80.64 - Revised alteration procedures for clarification and to remove unnecessary text.

Section 80.66 - Updated rule for clarification.

Section 80.119 - Changed wording instructing installer to certify instead of warrant the proper installation of the home and to provide the consumer with a written certification instead of an installation warranty. Also, other revisions were made for clarification.

Section 80.120 - Added the monthly shipment report rule that was previously located in repealed §80.203 and revised a rule reference.

Section 80.121 - Added text from repealed §80.200(b) relating to conveyance of a good and marketable title, 80.181 relating to providing the 162 Notice, and 80.182 relating to providing the 163 Disclosure. Other text updated for clarification and relocated disclosure forms associated with §80.181 and §80.182 to new Subchapter I (Forms).

Section 80.122 - Revised rule for clarification.

Section 80.123 - Revised rule for clarification and added a new section that explains new and renewed licenses will not be valid if all required fees are not paid.

Section 80.124 - Added new section that allows retailer to deduct fees from the deposit amount if the consumer owes for upgrades added to a home.

Section 80.125 - Updated rule for clarification and added a section requiring disclosure of license number of the person advertising.

Section 80.126 - Updated rule for consistency and clarification.

Section 80.127 - Updated rule for clarification and added new sections to include text from repealed §80.129(g) - (m).

Section 80.128 - Updated reference to "working days" to "business days."

New §80.129 - Replacing repealed rule with new rule that explains the department offers alternative dispute resolution. Moved relevant text in the repealed rule to §80.127 and moved the Enforcement Matrix figure in subsection (g) to §80.240(a)(12).

Section 80.130 - Updated rule for clarification.

Section 80.131 - Updated rule for clarification.

Section 80.132 - Updated rule for clarification.

Section 80.133 - Updated rule by changing "department" from uppercase to lowercase for consistency.

Section 80.135 - Updated rule for clarification.

Section 80.183 - Updated rule for clarification.

Section 80.205 - Updated rule by keeping the section on Inventory Finance Liens, deleted the unnecessary sections on Release of Liens and Foreclosure or Repossession and moved the section on right of survivorship to §80.201.

New §80.240 is in new Subchapter H relating to Tables and Figures. The tables from various rules are located in subsection (a) and the figures are located in subsection (b) for easier referencing.

Figure: 10 TAC §80.240(a)(1) - Maximum Spacing for Diagonal Ties.

Figure: 10 TAC §80.240(a)(2) - Minimum Number of Diagonal Ties.

Figure: 10 TAC §80.240(a)(3) - Maximum Spacing for Diagonal Ties per side of the Assembled Unit.

Figure: 10 TAC §80.240(a)(4) - Bracket Installation - Maximum Centerline Wall Opening for Column Uplift Brackets.

Figure: 10 TAC §80.240(a)(5) - Floor Connections - Wind Zone I and II.

Figure: 10 TAC §80.240(a)(6) - Roof Connections - Fastener Type and Spacing.

Figure: 10 TAC §80.240(a)(7) - Main Panel Box Feeder Conductor Sizes.

Figure: 10 TAC §80.240(a)(8) - Footer Capacities.

Figure: 10 TAC §80.240(a)(9) - Pier Loads without Perimeter Supports.

Figure: 10 TAC §80.240(a)(10) - Pier Loads with Perimeter Supports.

Figure: 10 TAC §80.240(a)(11) - Mating Line Column Loads.

Figure: 10 TAC §80.240(a)(12) - Enforcement Matrix.

Figure: 10 TAC §80.240(b)(1) - Counties Located in Wind Zone II.

Figure: 10 TAC §80.240(b)(2) - Anchor Installation.

Figure: 10 TAC §80.240(b)(3) - Placement of Stabilizing Plates.

Figure: 10 TAC §80.240(b)(4) - Wind Zone I Installation (Single & Multi-Section).

Figure: 10 TAC §80.240(b)(5) - Diagonal Strap Placement for Piers Exceeding 36 in. in Height.

Figure: 10 TAC §80.240(b)(6) - Diagonal and Vertical Ties.

Figure: 10 TAC §80.240(b)(7) - Typical Installation Details.

Figure: 10 TAC §80.240(b)(8) - Anchor Span.

Figure: 10 TAC §80.240(b)(9) - Typical Longitudinal Stabilizing Device. NOTE: Because the Department no longer employs an engineer, this proposed drawing has not been reviewed or approved by a Department engineer.

Figure: 10 TAC §80.240(b)(10) - Longitudinal Ties.

Figure: 10 TAC §80.240(b)(11) - Mating Line Surfaces.

Figure: 10 TAC §80.240(b)(12) - Floor Connections.

Figure: 10 TAC §80.240(b)(13) - Endwall Connections.

Figure: 10 TAC §80.240(b)(14) - Roof Connection.

Figure: 10 TAC §80.240(b)(15) - Exterior Roof Close Up.

Figure: 10 TAC §80.240(b)(16) - HVAC (Heat/Cooling) Duct Crossover.

Figure: 10 TAC §80.240(b)(17) - Multi-Section Water Crossover Connections.

Figure: 10 TAC §80.240(b)(18) - Drain, Waste and Vent Floor Piping System.

Figure: 10 TAC §80.240(b)(19) - Chassis Bonding.

Figure: 10 TAC §80.240(b)(20) - Electrical Crossover.

Figure: 10 TAC §80.240(b)(21) - Fuel Gas Pipe Crossover Connections.

Figure: 10 TAC §80.240(b)(22) - Footer Configurations. NOTE: Because the Department no longer employs an engineer, this proposed drawing has not been reviewed or approved by a Department engineer.

Figure: 10 TAC §80.240(b)(23) - Pier Design (Single and Multi-Section Stack). NOTE: Because the Department no longer employs an engineer, this proposed drawing has not been reviewed or approved by a Department engineer.

Figure: 10 TAC §80.240(b)(24) - Perimeter Pier Front & Side View.

Figure: 10 TAC §80.240(b)(25) - Typical Multi-Section Pier Layout.

Figure: 10 TAC §80.240(b)(26) - Typical Single Section Pier Layout.

Figure: 10 TAC §80.240(b)(27) - Determining Column Load and Marriage Line Elevation.

New §80.260 is in new Subchapter I relating to Forms. The required forms from various rules are located subsection (a) and the optional forms are located in subsection (b) for easier referencing.

Figure: 10 TAC §80.260(a)(1) - Site Preparation Notice.

Figure: 10 TAC §80.260(a)(2) - Consumer Disclosure Statement.

Figure: 10 TAC §80.260(a)(3) - 163 Disclosure - Choosing a Loan to Buy a Manufactured Home.

Figure: 10 TAC §80.260(a)(4) - Notice of Installation (Form T).

Figure: 10 TAC §80.260(a)(5) - Estimate for Reassigned Warranty Work.

Figure: 10 TAC §80.260(a)(6) - Application for Statement of Ownership and Location.

Figure: 10 TAC §80.260(a)(7) - Release or Foreclosure of Lien (Form B).

Figure: 10 TAC §80.260(a)(8) - Quick Processing Form.

Figure: 10 TAC §80.260(a)(9) - Form M.

Figure: 10 TAC §80.260(a)(10) - Affidavit of Fact for Right of Survivorship.

Figure: 10 TAC §80.260(b)(1) - Spanish Version of Consumer Disclosure Statement.

Figure: 10 TAC §80.260(b)(2) - Spanish Version of 163 Disclosure - Choosing a Loan to Buy a Manufactured Home.

Timothy K. Irvine, Executive Director of the Manufactured Housing Division of the Texas Department of Housing and Community Affairs, has determined that for the first five-year period that these new and amended sections as proposed are in effect there will be no fiscal implications for state or local government as a result of enforcing or administering these sections.

The following is the anticipated economic costs to persons/businesses that are required to comply with the proposed rules.

Section 80.20(b)(1) increases the installation reporting fee for multi-section homes from $75 to $150. There is no increase for single section homes.

Section 80.20(j)(4) increases the fee for correction of an SOL from $25 to $55, which is the original fee before the rule changed to $25 in September 2004.

Except for the above, there are no other proposed new and amended sections expected to have material economic costs to persons/businesses that are required to comply with these sections as proposed.

Mr. Irvine also has determined that for each year of the first five years these new and amended sections as proposed are in effect the public benefit as a result of enforcing the sections will be: organize rules by related subjects more logically; eliminate unnecessary or redundant verbiage; clean up areas of confusion and conflict; make the rules more useful, practical and as understandable as possible; clarify responsibilities that will increase compliance; and assure that the rules embrace a balanced overall approach that enhances compliance for the benefit of both the industry and consumers while accommodating the needs of related industries.

Comments may be submitted to Mr. Timothy K. Irvine, Executive Director of the Manufactured Housing Division, of the Texas Department of Housing and Community Affairs, P. O. Box 12489, Austin, Texas 78711-2489 or by e-mail at the following address tim.irvine@tdhca.state.tx.us. The deadline for comments is 30 days after publication in the Texas Register .

Subchapter A. CODES AND STANDARDS

10 TAC §80.10

The amended section is proposed under the Texas Manufactured Housing Standards Act, Occupations Code, Subtitle C, Chapter 1201, §1201.052, which provides the Department with authority to amend, add, and repeal rules governing the Manufactured Housing Division of the Department and under Texas Government Code, Chapter 2306, §2306.603, which authorizes the director to adopt rules as necessary to administer and enforce the manufactured housing program through the Manufactured Housing Division.

No other statute, code, or article is affected by the proposed amendment.

§80.10.Texas Manufactured Housing Standards Code.

The standards and requirements for the installation and construction of manufactured housing adopted by the director in accordance with §1201.251(a)(1) of the Texas Manufactured Housing Standards Act (Standards Act) are as follows:

(1) The construction standards set out in Title VI of the Housing and Community Development Act of 1974, as the same may be amended from time to time, or under any official rule, official interpretation, or adopted standard issued or adopted by the Department of Housing and Urban Development under such law;

(2) The installation standards set forth in this chapter; and

(3) Applicable standards for installation components established by

(A) Chapter 43 of the latest edition of the International Residential Code;

(B) The stabilizing component destruction test failure criteria of the FMHCSS (24 CFR, Part 3280) and the latest edition of the International Residential Code, Appendix E; and

(C) The American Wood Preserver's Association and referenced by the latest edition of the International Residential Code Preservation for treated (PT) wood components.

(4) Collectively, the foregoing, together with the Standards Act and these rules, are referred to as the Texas Manufactured Housing Standards Code ("the Code").

[ (a) The Texas Manufactured Housing Standards Code for HUD-Code manufactured homes shall be the Federal Standards established under Title VI of the Housing and Community Development Act of 1974 and each change, amendment, or requirement shall become effective in conjunction with the effective date set by the federal program.]

[ (b) The historical record of standards adopted for manufactured homes in accordance with the Standards Act, is as follows:]

[ (1) Prior to December 11, 1969: none;]

[ (2) December 12, 1969 - August 31, 1971: American National Standards Institute (ANSI), A119.1-1963, plumbing, heating and electrical;]

[ (3) September 1, 1971 - December 15, 1971: none;]

[ (4) December 15, 1971 - February 16, 1972: ANSI, A119.1-1969, plumbing, heating and electrical;]

[ (5) February 17, 1972 - January 31, 1973: ANSI, A119.1-1973, plumbing, heating and electrical;]

[ (6) February 1, 1973 - September 19, 1973: ANSI, A119.1-1973, plumbing, heating, electrical and construction;]

[ (7) September 20, 1973 - August 31, 1974: ANSI, A119.1-1973, plumbing, heating, electrical and construction;]

[ (8) September 1, 1974 - June 14, 1976: ANSI, A119.1-1974, plumbing, heating, electrical and construction; and]

[ (9) June 15, 1976 - Future: HUD-Code - National Manufactured Home Construction and Safety Standards, Part 3280, promulgated by the United States Department of Housing and Urban Development (HUD), Code of Federal Regulations (CFR), Title 24.]

This agency hereby certifies that the proposal has been reviewed by legal counsel and found to be within the agency's legal authority to adopt.

Filed with the Office of the Secretary of State on February 14, 2005.

TRD-200500648

Timothy K. Irvine

Executive Director, Manufactured Housing Division

Texas Department of Housing and Community Affairs

Earliest possible date of adoption: March 27, 2005

For further information, please call: (512) 475-2206


Subchapter B. DEFINITIONS

10 TAC §80.11

The amended section is proposed under the Texas Manufactured Housing Standards Act, Occupations Code, Subtitle C, Chapter 1201, §1201.052, which provides the Department with authority to amend, add, and repeal rules governing the Manufactured Housing Division of the Department and under Texas Government Code, Chapter 2306, §2306.603, which authorizes the director to adopt rules as necessary to administer and enforce the manufactured housing program through the Manufactured Housing Division.

No other statute, code, or article is affected by the proposed amendment.

§80.11.Definitions.

Terms used herein that are defined in the Code and the Standards Act have the meanings ascribed to them therein. The following words and terms, when used in this chapter, shall have the following meanings, unless the context clearly indicates otherwise:

[ (1) Alteration--The replacement, addition, and modification or removal of any equipment or its installation after sale by the manufacturer to a retailer, but prior to sale and installation to a purchaser which may affect the construction, fire safety, occupancy plumbing, heat-producing, or electrical system. An alteration is deemed to be prior to sale if the alteration is part of the retail sales contract. It includes any modification made in the manufactured home which may affect the compliance of the home with the standards, but it does not include the repair or replacement of a component or appliance requiring plug-in to an electrical receptacle where the replaced item is of the same configuration and rating as the one being replaced. It also does not include the addition of an appliance requiring "plug-in" to an electrical receptacle, which appliance was not provided with the manufactured home by the manufacturer, if the rating of the appliance does not exceed the rating of the receptacle to which it is connected (FMHCSS §3287.7(c)).]

(1) [ (2) ] Anchoring components--Any component which is attached to the manufactured home and is designed to resist the horizontal and vertical forces imposed on the manufactured home as a result of wind loading. These components include auger anchors, rock anchors, slab anchors, ground anchors, stabilizing plates, connection bolts, j-hooks, buckles, and split bolts.

(2) [ (3) ] Anchoring equipment--Straps, cables, turnbuckles, and chains, including tensioning devices, which are used with ties to secure a manufactured home to anchoring components or other [ approved ] devices.

(3) [ (4) ] Anchoring systems--Combination of ties, anchoring components, and anchoring equipment that will resist overturning and lateral movement of the manufactured home from wind forces.

(4) [ (5) ] APA--Administrative Procedure Act, Texas Government Code, Chapter 2001.

[ (6) Attachment--With respect to a manufactured home, that it has been installed in accordance with the Department’s rules and connected to any one or more utilities including, but not limited to, electricity, water, natural gas, propane or bottled gas, or wastewater service. For purposes of determining whether a manufactured home is attached, the presence of installation deviations or violations shall not invalidate the home’s status as being attached.]

[ (7) Board--Governing Board of the Manufactured Housing Division of the Texas Department of Housing and Community Affairs.]

(5) Business days--Includes every day on the calendar except Saturday, Sunday, and federal and state holidays.

[ (8) Business use--Any use other than for dwelling purposes.]

[ (9) Calendar days--Includes every day on the calendar.]

(6) [ (10) ] Certificate of Attachment--A certificate issued by the department to the person who surrenders the Manufacturer's Certificate of Origin or document of title when the home has been permanently attached [ affixed ] to real estate. Certificates of Attachment are no longer issued after June 18, 2003.

(7) [ (11) ] Chattel Mortgage or Consumer Loan-- Any loan that is not subject to the Real Estate Settlement Procedures Act (RESPA). [ A loan subject to Chapter 347, Texas Finance Code, that is not a mortgage loan. ]

(8) [ (12) ] Coastline--The shoreline that forms the boundary between the land and the Gulf of Mexico or a bay or estuary connecting to the Gulf of Mexico that is more than five miles wide.

(9) [ (13) ] Credit document-- All [ The credit sale contract or the loan instruments including all ] the written agreements between the consumer and creditor that describe or are required in connection with an actual [ relate to the ] credit transaction.

(10) [ (14) ] Creditor--A person involved in a credit transaction who:

(A) extends or arranges the extension of credit; or

(B) is a retailer or broker as defined in the Standards Act and participates in arranging for the extension of credit.

[ (15) Creditor-Lender--A person that is involved in extending or arranging for credit in inventory financing secured by manufactured housing.]

(11) [ (16) ] Custom designed stabilization system--An anchoring and support system that is not an approved method as prescribed by the state generic standards, manufacturer's installation instructions, or other systems pre-approved by the department.

(12) [ (17) ] DAPIA--The Design Approval Primary Inspection Agency.

[(18) Defect--A failure to comply with an applicable federal manufactured home safety and construction standard that renders the manufactured home or any part or component thereof not fit for the ordinary use for which it was intended, but does not result in an unreasonable risk of injury or death to occupants of the affected manufactured home (FMHCSS §3282.7(j)).]

[ (19) Department--The Manufactured Housing Division of the Texas Department of Housing and Community Affairs (TDHCA).]

[ (20) Department inspector--An inspector who is an employee of the Manufactured Housing Division of the Texas Department of Housing and Community Affairs or an inspector who is an employee of an entity performing inspection services under contract with the department.]

(13) [ (21) ] Deposits--Money or other consideration given by a consumer to a retailer, salesperson, or agent of a retailer to hold a home in inventory for subsequent purchase or to special order a home for subsequent purchase.

(14) [ (22) ] Diagonal tie--A tie intended to primarily resist horizontal forces, but which may also be used to resist vertical forces.

[ (23) Director--The Executive Director of the Manufactured Housing Division of the Texas Department of Housing and Community Affairs (TDHCA).]

(15) [ (24) ] Down Payment--An amount, including the value of any property used as a trade-in, paid to a retailer to reduce the cash price of goods or services purchased in a credit sale transaction.

(16) [ (25) ] Dwelling unit--One or more habitable rooms which are designed to be occupied [ by one family with facilities ] for living[ , sleeping, cooking and eating ].

(17) [ (26) ] FMHCSS--Federal Manufactured Home Construction and Safety Standards that implement the National Manufactured Home Construction and Safety Standards Act of 1974, 42 USC 5401, et seq., as amended from time to time [ and means a reasonable standard for the construction, design, and performance of a manufactured home which meets the needs of the public including the need for quality, durability, and safety ].

(18) [ (27) ] Footing--That portion of the support system that transmits loads directly to the soil.

(19) [ (28) ] Ground anchor--Any device at the manufactured home site designed to transfer manufactured home anchoring loads to the ground.

[ (29) HUD-Code manufactured home--A structure constructed on or after June 15, 1976, according to the rules of HUD, transportable in one or more sections, which, in the traveling mode, is eight body feet or more in width or 40 body feet or more in length, or, when erected on site, is 320 or more square feet, and which is built on a permanent chassis and designed to be used as a dwelling with or without a permanent foundation when connected to the required utilities, and includes the plumbing, heating, air-conditioning, and electrical systems. The term does not include a recreational vehicle as that term is defined by 24 CFR, §3282.8(g).]

[ (30) Imminent safety hazard--A hazard that presents an imminent and unreasonable risk of death or severe personal injury that may or may not be related to failure to comply with an applicable federal manufactured home construction and safety standard (FMHCSS §3282.7(q)).]

(20) [ (31) ] Independent testing laboratory--An agency or firm that tests products for conformance to standards and employs at least one engineer or architect licensed in at least one state.

[ (32) Installation information--A term used to describe the reports used to inform the department of information needed to perform installation inspections (includes Notice of Installation).]

(21) Inventory Lender--A person that is involved in extending or arranging for credit in inventory financing secured by manufactured housing.

(22) [ (33) ] IPIA--The Production Inspection Primary Inspection Agency which evaluates the ability of manufactured home manufacturing plants to follow approved quality control procedures and/or provides ongoing surveillance of the manufacturing process.

[ (34) Lien--A security interest that is created by any kind of lease, conditional sales contract, deed of trust, chattel mortgage, trust receipt, reservation of title or other security agreement of whatever kind or character, if an interest, other than an absolute title, is sought to be held or given in a manufactured home, and any lien on a manufactured home that is created or given by the constitution or a statute.]

(23) Longitudinal ties--designed to prevent lateral movement along the length of the home.

(24) [ (35) ] Long-Term Lease--For the purpose of determining whether or not the owner of a manufactured home may elect to treat the home as real property, is a lease on land to which the manufactured home has been attached and which:

(A) has been approved by each lienholder for the manufactured home by placing on file with the department written consent to have the home treated as real property; or

(B) is for at least five years if the home is not financed.

(25) [ (36) ] Main frame-- A chassis or structure serving a similar purpose [ The structural components on which the body of the manufactured home is mounted ].

[ (37) Manufactured home--A HUD-Code manufactured home or a mobile home and collectively means and refers to both.]

(26) [ (38) ] Manufactured home identification numbers--For the purpose of maintaining ownership and location [ purposes of title ] records, the numbers shall include the HUD label number(s) and the serial number(s) imprinted or stamped on the home in accordance with HUD departmental regulations. For homes manufactured prior to June 15, 1976, the Texas seal number, as issued by the department, shall be used instead of the HUD label number. If a home manufactured prior to June 15, 1976, does not have a Texas seal, or if a home manufactured after June 15, 1976, does not have a HUD label, a Texas seal shall be purchased from the department and attached to the home in upper left corner on tongue end and used for identification in lieu of the HUD label number.

(27) [ (39) ] Manufactured home site--That area of a lot or tract of land on which a manufactured home is installed.

[ (40) Mobile home--A structure that was constructed before June 15, 1976, transportable in one or more sections, which, in the traveling mode, is eight body feet or more in width or 40 body feet or more in length, or, when erected on site, is 320 or more square feet, and which is built on a permanent chassis and designed to be used as a dwelling with or without a permanent foundation when connected to the required utilities, and includes the plumbing, heating, air-conditioning, and electrical systems.]

(28) [ (41) ] Permanent foundation-- A foundation which meets the requirements of §80.54 of this title (relating to Requirements for the Installation of Manufactured Homes) and was constructed according to drawings, as required by that section, which state that the foundation is a permanent foundation for a manufactured home. [ A system of supports and securements, including piers, either partially or entirely below grade which is constructed or certified in accordance with the criteria outlined in §80.52(a) and (b), of this title (relating to Permanent Foundation Performance Criteria). ]

[ (42) Permanently affixed--Having been anchored to the real estate by attachment to a permanent foundation.]

[ (43) Rebuild--To make a salvaged manufactured home habitable in accordance with §80.66 of this title (relating to Rebuilding or Repairing a "Salvaged" Manufactured Home).]

[ (44) Rebuilder--Any person, within the state, who has been licensed by the department to rebuild a salvaged manufactured home, as defined in §1201.461 the Standards Act, in accordance with the rules and regulations of the department.]

[ (45) Refurbish--To make a nonhabitable manufactured home or section habitable by repairing, adding, replacing, modifying, or removing components.]

[ (46) Serious defect--Any failure to comply with an applicable federal manufactured home construction and safety standard that renders the manufactured home or any part thereof not fit for the ordinary use for which it was intended and which results in an unreasonable risk of injury or death to occupants of the affected manufactured home (FMHCSS §3282.7(gg)).]

(29) [ (47) ] Shim--A wedge-shaped piece of [ cedar, oak, walnut, pecan, gum, ash, hickory, elm, or other comparable ] hardwood or other accepted material not to exceed one (1) inch vertical (actual) height.

(30) [ (48) ] Stabilizing components--All components of the anchoring and support system such as piers, footings, ties, anchoring equipment, ground anchors and any other equipment, which supports the manufactured home and secures it to the ground.

(31) Stabilization system--a combination of the anchoring and support system.

[ (49) Standards Act--Texas Manufactured Housing Standards Act, Occupations Code, Subtitle C, Chapter 1201.]

[ (50) Statement of Ownership and Location--means a statement, issued by the Department on the prescribed form, based on a completed application for Statement of Ownership and Location, accompanied by the required fee and all required supporting documentation.]

(32) [ (51) ] Support system--A combination of footings, piers, caps and shims that support the manufactured home.

(33) [ (52) ] TDHCA--The Manufactured Housing Division of the Texas Department of Housing and Community Affairs (department) [ (Department) ].

[ (53) TMHSA--Texas Manufactured Housing Standards Act, Occupations Code, Subtitle C, Chapter 1201.]

(34) [ (54) ] Used home--Any manufactured home (or mobile home) [ for ] which has been installed and occupied for living [ a document of title as previously been issued by an appropriate agency of any state or which has been occupied ].

(35) [ (55) ] Vertical tie--A tie intended primarily to resist the uplifting and overturning forces.

[ (56) Wind Zone I--All Texas counties not in Wind Zone II.]

[ (57) Wind Zone II--Aransas, Brazoria, Calhoun, Cameron, Chambers, Galveston, Jefferson, Kenedy, Kleberg, Matagorda, Nueces, Orange, Refugio, San Patricio, and Willacy counties.]

[ (58) Working days--Includes every day on the calendar except Saturday, Sunday, and federal and state holidays.]

This agency hereby certifies that the proposal has been reviewed by legal counsel and found to be within the agency's legal authority to adopt.

Filed with the Office of the Secretary of State on February 14, 2005.

TRD-200500649

Timothy K. Irvine

Executive Director, Manufactured Housing Division

Texas Department of Housing and Community Affairs

Earliest possible date of adoption: March 27, 2005

For further information, please call: (512) 475-2206


Subchapter C. FEE STRUCTURE

10 TAC §80.20

The amended section is proposed under the Texas Manufactured Housing Standards Act, Occupations Code, Subtitle C, Chapter 1201, §1201.052, which provides the Department with authority to amend, add, and repeal rules governing the Manufactured Housing Division of the Department and under Texas Government Code, Chapter 2306, §2306.603, which authorizes the director to adopt rules as necessary to administer and enforce the manufactured housing program through the Manufactured Housing Division.

No other statute, code, or article is affected by the proposed amendment.

§80.20.Fees.

(a) Annual License Fees and Renewal Fees:

(1) $425 for each manufacturer's plant license;

(2) $275 for each retailer's sales license;

(3) $275 for each rebuilder's license;

(4) $175 for each broker's license;

(5) $175 for each installer's license; and

(6) $100 for each salesperson's license , which must be submitted to the department in the form of a cashier’s check or money order .

(b) Installation Fees:

(1) There is a reporting fee of $75 for the installation of a single section and $150 for a multi-section [ each ] manufactured home [ which is not installed on a permanent foundation ].

(2) The reporting fee must be submitted to the department with the completed Notice of Installation (Form T) within thirty (30) days of the original sale or within ten (10) days of a secondary move [ There is a reporting fee of $150 for the installation of a manufactured home permanently affixed to real estate or on a permanent foundation ].

[ (3) Installation fees shall be submitted to the department as follows:]

[ (A) When the installation occurs in conjunction with a title transfer, the fee must be submitted to the department along with the application for title and the Notice of Installation Affidavit; or]

[ (B) For secondary moves (when there is no title transfer), the fee must be submitted to the department along with a completed Notice of Installation Affidavit within ten (10) working days following the installation date.]

(3) [ (4) ] Fee distributions to local governmental entities performing inspection functions pursuant to contract with the department shall be made in accordance with department procedures and the provisions of the contract.

[ (c) Alteration Fee: There is a fee of $60 per hour or a minimum fee of $60 for the inspection of alterations made upon the structure, plumbing, heating, or electrical systems of manufactured homes. The fee is paid to the department by the person making the alterations. The person shall also reimburse the department for mileage and per diem incurred by department personnel to and from the place of inspection.]

(c) [ (d) ] Seal Fee: There is a fee of $35 for the issuance of Texas Seals. Any person who sells, exchanges, lease purchases, or offers for sale, exchange, or lease purchase a used HUD-Code manufactured home manufactured after June 15, 1976, that does not have a HUD label affixed, or a used mobile home manufactured prior to June 15, 1976, that does not have a Texas Seal affixed shall file an application to the department for a Texas Seal. The application shall be accompanied by the seal fee of $35 per section made payable to the department.

(d) [ (e) ] Monitoring Fee: There is a fee, as required by HUD, to be paid by each manufacturer in this state for each HUD-Code manufactured home produced. The monitoring inspection fee is established by the secretary of HUD, (pursuant to 24 CFR §3282.307) who shall distribute the fees collected from all manufacturers among the approved and conditionally approved states based on the number of new homes whose first location after leaving the manufacturing plant is on the premises of distributor, retailer, or purchaser in that state, and the extent of participation of the state in the joint monitoring program established under the National Manufactured Housing Construction and Safety Standards Act of 1974.

(e) [ (f) ] Homeowner's Temporary Installer's License: There is a fee of $100 for the issuance of a homeowner's temporary installer's license, which shall also include the cost of the installation inspection. The fee shall be made payable to the department.

(f) [ (g) ] Education Fee: Each attendee at the course of instruction in the law and consumer protection regulations for license applicants shall be assessed a fee of $250. If a manufacturer requests the training be performed at his or her facility, the manufacturer shall reimburse the department for the actual costs of the training session (educational fee plus actual cost of travel).

(g) Fees for department-provided Continuing Education: There is a fee of $100 for attending eight hours of continuing education provided by the department.

(h) Habitability Inspection:

(1) There is a fee of $150 for the inspection of a manufactured home which is to be designated for residential use [ titled for use as a residence ] after having [ the title has ] been previously designated [ canceled ] for business use [ or to become real estate ]. The purpose of the inspection is to determine if the home is habitable as defined by §1201.453 [ §8 ] of the Standards Act. The fee must accompany a written request for inspection and must be submitted either prior to or in connection with the submission of an Application for Statement of Ownership and Location. [ The fee shall accompany a Form A to apply for reinstatement of the title along with those documents set forth in §80.207 of this title (relating to Reinstatement of Canceled Documents of Title). The person requesting the inspection for the use change of a manufactured home shall be charged for mileage and per diem incurred by department personnel traveling to and from the location of the manufactured home. The inspector shall advise the consumer of the charges incurred and no title shall be issued until all fees have been paid. ]

(2) There is a fee of $200 for the plan review and inspection of a salvaged manufactured home which is to be rebuilt . The purpose of the inspection is to determine if the home is habitable so that it may be designated for residential use. [ for reinstatement of the title. The fee shall accompany a written request for the inspection. The rebuilder shall also be charged for mileage and per diem incurred by department personnel traveling to and from the location of the home. See §80.66 of this title (relating to Rebuilding or Repairing a "Salvaged" Manufactured Home). The inspector shall advise the rebuilder of the charges incurred and no title shall be issued until all fees have been paid. ]

(A) The fee and required notification shall be submitted in accordance with §80.66 of this title (relating to Rebuilding or Repairing a "Salvaged" Manufactured Home).

(B) The rebuilder shall also be charged for mileage and per diem incurred by department personnel traveling to and from the location of the home.

(C) The inspector shall advise the rebuilder of the charges incurred, and no Statement of Ownership and Location shall be issued until all fees have been paid.

(i) Consumer Complaint Inspection:

(1) There is a fee of $150 for the initial inspection of a consumer's home in accordance with a consumer complaint when requested by a license holder or party other than a consumer. The fee shall accompany a written request for the inspection.

(2) There is a fee of $150 for the reinspection of a consumer's home. The fee shall be paid by the party deemed responsible by the department.

(j) Fees Relating to Statements of Ownership and Location. Except as provided herein, all processing fees shall be submitted in the form of a cashier's check or money order payable to the Texas Department of Housing and Community Affairs or TDHCA. The fee shall accompany the required documents forwarded to the Manufactured Housing Division of the department at its principal office in Austin. [ Titles: Fees relating to titles and title transactions are set forth in §80.202 of this title (relating to Fees for Title Documents). ]

(1) A fee of $55 will be required for the issuance of a Statement of Ownership and Location;

(2) A fee of $1.50 will be required for certified copies requested other than one certified copy of a Statement of Ownership and Location sent to the owner and one that is sent to the lienholder;

(3) There shall be a fee of $55 for Quick Processing Service in addition to the $55 processing fee for each application for Statement of Ownership and Location.

(A) Quick Processing Service shall be defined as the processing of an Application for Statement of Ownership and Location within three (3) business days from the day the complete application is received in the Manufactured Housing Division. The department will refund the Quick Processing Service fee if the completed application is not processed within the required time.

(B) If an applicant desires Quick Processing, the Quick Processing form provided in §80.260 of this title (relating to Required and Optional Forms) must be completed and attached to the front of the application for the application to be deemed complete.

(C) If the Quick Processing form is missing or incomplete or if any other necessary documents or fees are deficient, any delays in processing caused by such will not entitle the payer to a refund of the Quick Processing fee or any other required processing fee.

(D) If Quick Processing is requested but the Quick Processing fee is not paid, the application will receive regular processing.

(E) All Quick Processing applications must be submitted by overnight service or delivered in-person.

(F) If Quick Processing is not completed within three (3) business days, as required, the Quick Processing fee only will be refunded.

(G) All Statement of Ownership and Locations will be sent via regular mail unless a pre-paid overnight envelope is provided.

(4) If a correction of a document is required as a result of a mistake by the department, the issuance of a new document shall not require a fee. However, if the error was not made by the department, a request for correction of the error must be made on a completed Application for Statement of Ownership and Location and submitted to the department along with the required fee of $55 and any necessary supporting documentation.

(5) All persons licensed with the department as a manufacturer, retailer, broker, or installer may submit company or business firm checks in payment of any fee described herein. All state or federally chartered banks, savings banks or savings institutions and all commercial lenders or mortgage bankers who extend credit for the retail purchase of manufactured homes may also pay any fees with company or business firm checks at the discretion of the department. All checks shall be made payable to the Texas Department of Housing and Community Affairs or TDHCA.

(6) When multiple applications are submitted, the Form M provided in §80.260 of this title (relating to Required and Optional Forms) must be completed and attached to the front of the applications to identify each application and reconcile the fee for each application with the total amount of the payment.

This agency hereby certifies that the proposal has been reviewed by legal counsel and found to be within the agency's legal authority to adopt.

Filed with the Office of the Secretary of State on February 14, 2005.

TRD-200500650

Timothy K. Irvine

Executive Director, Manufactured Housing Division

Texas Department of Housing and Community Affairs

Earliest possible date of adoption: March 27, 2005

For further information, please call: (512) 475-2206


Subchapter D. STANDARDS AND REQUIREMENTS

10 TAC §§80.53 - 80.59, 80.62, 80.64, 80.66

The new and amended sections are proposed under the Texas Manufactured Housing Standards Act, Occupations Code, Subtitle C, Chapter 1200, §1201.052, which provides the Department with authority to amend, add, and repeal rules governing the Manufactured Housing Division of the Department and under Texas Government Code, Chapter 2306, §2306.603, which authorizes the director to adopt rules as necessary to administer and enforce the manufactured housing program through the Manufactured Housing Division.

No other statute, code, or article is affected by the proposed new and amended rules.

§80.53. Requirements for Manufacturer's Designs and Installation Instructions [ Design Requirements ].

(a) With each new home, the manufacturer shall provide printed instructions which at a minimum must: [ Each new manufactured home shall be designed and constructed as a completely integrated structure capable of sustaining the design load requirements of the FMHCSS and shall be capable of transmitting the loads to anchoring systems without causing an unsafe deformation or an abnormal internal movement of the structure or its structural parts. ]

(1) specify the location, orientation and required capacity of stabilizing components on which the design is based;

(2) be filed with the department;

(3) be approved by the manufacturer's DAPIA; and

(4) contain DAPIA approval stamps, engineer or architect approval stamps, and the installation manual effective date on each page of the installation instructions or on the cover pages of bound installation manuals, unless an equivalent method of authentication is used for electronically filed documents.

(b) A manufacturer may file an appendix to the state's generic standards as a part of the manufacturer's DAPIA-approved installation instructions if the design of one or more of its homes requires a change in the generic standards to protect the structural integrity of the home. The appendix shall specify which provision of the generic standards is being changed and clearly set forth in detail the change that is necessary. Any such appendix that is filed with the department shall be incorporated under §80.59 of this title (relating to Exception to Generic Installation Standards) as part of the state's generic standards. [ Each new manufactured home shall have provisions for anchoring systems which, when properly designed and installed, will resist overturning and lateral movement of the manufactured home up to the respective design loads. ]

(c) At least thirty (30) calendar days prior to the effective date of any change, modification, or update to the manufacturer's installation instructions or any appendix, the manufacturer shall file such change, modification, or update with the department and mail a copy(s) to all the manufacturer's retailers. [ The provisions of this section shall be followed and the support and anchoring systems shall be designed by a licensed professional engineer or architect. ]

(d) The manufacturer shall file with the department additional copies of manufacturer's installation instructions for each model in the number specified by the department. If no number is specified, one copy of each such set of instructions will suffice. [ The manufacturer shall design homes to make provisions for the necessary support and anchoring systems, but is not required to provide the anchoring equipment. Printed installation instructions for support and anchoring systems for each model shall be filed with the department as required by the department. When the manufacturer's installation instructions provide for the main frame structure to be used as the point for connection to diagonal ties, no specific connecting devices need to be provided on the frame. Ties shall be designed and installed to prevent self disconnection when the ties are slack. For example, open end hooks shall have set screws or other mechanisms to prevent disconnection when there is slack in the strapping. ]

(e) The department will default to the generic standards, if discrepancies exist in the manufacturer's instructions. [ The manufacturer shall provide printed instructions with each new home specifying the location, orientation and required capacity of stabilizing components on which the design is based. The installer must use stabilizing components that have the required capacity and install them according to the anchor or stabilizing component manufacturer's current installation instructions. When soil auger anchor shafts are not installed in-line with the diagonal frame ties or the combined loads of two ties, approved stabilizer plates, or other approved methods, must be used in accordance with the installation instructions for the soil auger anchors and stabilizer plates. If a difficult soil, such as mixed soil and rock or caliche (heavily weathered limestone) that is not solid rock, exists at the homesite, the installer may install a home in accordance with the generic standards and §80.55(d)(4) of this title (relating to Anchoring Systems). ]

[ (f) The minimum number of ties required per side shall be sufficient to resist the wind load stated in the FMHCSS §3280.305(c).]

§80.54. Requirements [ Standards ] for the Installation of Manufactured Homes.

(a) When they are installed, all [ All ] manufactured homes shall be installed by a licensed installer to resist overturning and lateral movement of the home, and the installation must be completed in accordance with instructions appropriate for the Wind Zone where the home is to be installed as per one of the following:

(1) the home manufacturer's DAPIA-approved installation instructions;

(2) the state's generic standards set forth in §§80.55, 80.56, 80.57, 80.58 and their appendix in §80.59 of this title [ this section, §80.55 of this title (relating to Anchoring Systems), §80.56 of this title (relating to Multi-Section Connection Standards), and modified by any appendix filed in accordance with §80.51(a)(2) of this title (relating to Manufactured Home Installation Requirements) ];

(3) the instructions for a stabilization system registered with the department in accordance with §80.62 of this title (relating to Registration of Stabilizing Components and Systems); or [ a custom designed stabilization system; ]

(4) the instructions for a special stabilization system which; [ a stabilization system pre-approved by the department; or ]

(A) may or may not be a permanent foundation;

(B) is for a particular manufactured home or an identified class of manufactured homes to be installed at a particular area with similar soil properties according to county soil survey or other geotechnical reports; and

(C) is either:

(i) a pre-existing foundation for which a professional engineer or architect licensed in Texas has issued written approval for the installation of a particular home, and the written approval shall be submitted to the department with the installation report; or

(ii) installed in accordance with a custom designed stabilization system drawing that is stamped by a Texas licensed professional engineer or architect.

(I) A copy of the stabilization system drawing must be forwarded to the department along with the installation report.

(II) If the bottoms of the footings or piers are embedded more than 24 inches below the finished natural grade or engineered fill, it must be reported on the Permanent Foundation Report form and sent to the department at least ten (10) business days prior to the date of construction, along with the required fee.

[ (5) on a permanent foundation.]

(b) When a home is installed on a stabilization system registered with the department or a special stabilization system, the installer must follow the home manufacturer's DAPIA-approved installation instructions for any aspect of the installation that is not covered by the system's installation instructions or drawings.

(c) The installer must use stabilizing components that have the required capacity and install them according to the anchor or stabilizing component manufacturer's current installation instructions. All stabilizing components must be resistant to all effects of weathering including that encountered along the Texas gulf coast. Nonconcrete stabilizing components and systems for use within 1500 feet of the coastline shall be specifically certified for this use. Preservation treated (PT) wood components shall conform to the applicable standards issued by the American Wood Preserver's Association and referenced by the latest edition of the International Residential Code.

(d) [ (b) ] Site Preparation Responsibilities and Requirements:

(1) The purchaser of a manufactured home, new or used, is responsible for the proper preparation of the site where the manufactured home will be installed except as set forth in §80.57 of this title (relating to Generic Standards for Moisture and Ground Vapor Controls) [ subsection (g) of this section ]:

(A) In the case of a manufactured home that is to be installed in a manufactured home rental community (as defined in Local Government Code §232.007), the purchaser may not have the ability to control the preparation of the site. Therefore, the purchaser should confirm with the person who owns, leases, or manages the rental community that the site has been properly prepared as required by Property Code, §94.151.

(B) When a manufactured home is sold already installed it is not possible for the purchaser to prepare the site. Therefore, it is the responsibility of the seller, if the seller is a licensed retailer, to ensure that the site has been properly prepared.

(2) Whenever a licensed retailer intends to sell a manufactured home, regardless of where it is located or is to be located, the retailer is required to give the proposed purchaser the Site Preparation Notice, for signature by the consumer, in the form set forth in §80.260(a)(1) of this title (relating to Required and Optional Forms) [ subsection (g) of this section ] PRIOR to the execution of any binding sales agreement.

(3) Whenever a licensed installer proposes to move a used manufactured home, the installer is required to give the proposed purchaser the Site Preparation Notice, for signature by the consumer, in the form set forth in §80.260(a)(1) of this title (relating to Required and Optional Forms) [ subsection (g) of this section ] PRIOR to entering into a binding agreement to move that home.

(e) [ (c) ] If the retailer or installer provides the materials for skirting or contracts for the installation of skirting, the retailer or installer is responsible for installing [ the following: The retailer or installer shall install ] any required moisture and ground vapor control measures in accordance with the home installation instructions, specifications of a registered [ an approved ] stabilization system, or the generic standards and shall provide for the proper cross ventilation of the crawl space. If the purchaser or homeowner contracts with a person other than the retailer or installer for the skirting, the purchaser or homeowner is responsible for installing the moisture and ground vapor control measures and for providing for the proper cross ventilation of the crawl space.

(f) [ (d) ] Clearance: If the manufactured home is installed according to the state's generic standards, a minimum clearance of 18 inches between the ground and the bottom of the floor joists must be maintained. In addition, the installer shall be responsible for installing the home with sufficient clearance between the I-Beams and the ground so that after the crossover duct prescribed by the manufacturer is properly installed it will not be in contact with the ground. Refer to §80.56 of this title (relating to Generic Standards for Multi-Section Connections [ Connection ] Standards) for additional requirements for utility connections. It is strongly recommended that the installer not install the home unless all debris, sod, tree stumps and other organic materials are removed from all areas where footings are to be located.

(g) [ (e) ] Drainage: The purchaser is responsible for proper site drainage where the manufactured home (new or used) is to be installed unless the home is installed in a rental community. It is strongly recommended that the installer not install the home unless the exterior grade is sloped away from the home or another generally accepted [ approved ] method to prohibit surface runoff from draining under the home is provided. Drainage prevents water build-up under the home. Water build-up may cause shifting or settling of the foundation, dampness in the home, damage to siding and bottom board, buckling of walls and floors, delamination of floor decking and problems with the operation of windows and doors.

[ (f) Generic Moisture and Ground Vapor Controls:]

[ (1) If the manufactured home is installed according to the state's generic standards and the space under the home is to be enclosed with skirting and/or other materials provided by the retailer and/or installer, an access opening not less than 18 inches in any dimension and not less than three square feet in area shall be provided by the installer. The access opening shall be located so that any water supply and sewer drain connections located under the home are accessible for inspections. If a clothes dryer exhaust duct, air conditioning condensation drain, or combustion air inlet is present, the installer must pass it through the skirting to the outside. In addition, crawl space ventilation must be provided at the rate of minimum 1 square foot of net free area, for every 150 square feet of floor area. At least six openings shall be provided, one at each end of the home and two on each side of the home. The openings shall be screened or otherwise covered to prevent entrance of rodents (note: screening will reduce net free area). For example, a 16'x76' single section home has 1216 square feet of floor area. This 1216 square feet divided by 150 equals 8.1 square feet or 1166 square inches of net free area crawl space ventilation.]

[ (2) The retailer and/or installer must notify the purchaser that moisture and ground vapor control measures are required if the space under the home is to be enclosed. Water vapor build-up may cause dampness in the home, damage to siding and bottom board, buckling of walls and floors, delamination of floor decking and problems with the operation of windows and doors. The generic ground vapor control measure shall consist of a ground vapor retarder that is minimum 6 mil polyethylene sheeting or its equivalent, installed so that the area under the home is covered with sheeting and overlapped approximately 12 inches at all joints. Any tear larger than 18 inches long or wide must be taped using a material appropriate for the sheeting used. The laps should be weighted down to prevent movement. Any small tears and/or voids around construction (footings, anchor heads, etc.) are acceptable.]

[ (g) Notice: The site preparation notice to be given to the consumer shall be as follows:]

[ Figure: 10 TAC §80.54(g) ]

[ (h) Footers and Piers:]

[ (1) Proper sizing of footings depends on the load carrying capacity of both the piers and the soil. To determine the load bearing capacity of the soil, the installer may use any of the following methods:]

[ (A) Pocket penetrometer:]

[ (i) Test a typical area adjacent to or within 10 feet of the perimeter of the unit;]

[ (ii) Dig down to undisturbed soil. This should be a minimum of 1 square foot surface area; and]

[ (iii) Using the pocket penetrometer take seven (7) readings, eliminate the highest and the lowest and average the remaining five (5).]

[ (B) Soil surveys from the U.S. Department of Agriculture;]

[ (C) Values from tables of allowable or presumptive bearing capacities given in local building codes. Such tables are commonly available from the local authority having jurisdiction; or]

[ (D) Any other test data from soil analysis reports.]

[ (2) The footing must be placed on firm, undisturbed soil, or fill compacted to at least 90% of its maximum relative density. Installation on loose, noncompacted fill may invalidate the home's limited warranty.]

[ (3) Footer configurations:]

[ Figure: 10 TAC §80.54(h)(3) ]

[ (4) Footer sizing and capacities: The following tables represent maximum loads and spacings based on footer size and soil bearing capacity. Other approved footers may be used if equal or greater in bearing area than those footer sizes tabulated. ]

[ Figure: 10 TAC §80.54(h)(4) ]

[ (5) Piers and pier spacings: One of the most important parts of home installation is proper pier installation. Incorrect size, location or spacing of piers may cause serious structural damage to the home. Spacing and location of piers shall be in accordance with the tables listed in these standards (Table 3B, without perimeter piers; Table 3C, with perimeter piers).]

[ (A) Spacing shall be as even as practicable along each main I-Beam. Pier spacing may exceed tabulated values up to 30% so long as the total pier count remains the same. End piers are to be located within 24 inches of the end of the main frame.]

[ (B) Piers shall extend at least 6 inches from the centerline of the I-Beam or be designed to prevent dislodgment due to horizontal movement of less than 4 inches.]

[ (C) Load bearing supports or devices shall be listed by an independent testing laboratory, nationally recognized inspection agency, or other nationally recognized organization and approved by the department. Engineers or architects licensed in Texas may design load bearing supports or devices for a single installation. A copy of the design for this particular home and site shall be provided to the department before the home is installed, but department approval is not required.]

[ (D) Sidewall openings greater than 4 feet shall have perimeter piers located under each side of the opening, i.e. patio doors, recessed porches/entries, bay windows and porch posts. Perimeter piers for openings are not required for endwalls.]

[ (6) Pier design: Piers shall be constructed per the following details:]

[ Figure: 10 TAC §80.54(h)(6) ]

[ (A) Shimming (if needed): Hardwood shims are commonly used as a means for leveling the home and filling any voids left between the bottom flange of the I-Beam and the top of the pier cap. Wedge shaped shims must be installed from both sides of the I-Beam to provide a level bearing surface. The allowable height must not exceed 1 inch. Shims shall be a minimum of 3 inches wide and 6 inches long. Over shimming should be avoided.]

[ (B) Table 3B - Pier loads (pounds) at tabulated spacings WITHOUT perimeter supports:]

[ Figure: 10 TAC §80.54(h)(6)(B) ]

[ (C) Table 3C - Pier loads (pounds) at tabulated spacings WITH perimeter supports:]

[ Figure: 10 TAC §80.54(h)(6)(C) ]

[ (7) Typical multi-section pier layout:]

[ Figure: 10 TAC §80.54(h)(7) ]

[ (8) Typical single section pier layout:]

[ Figure: 10 TAC §80.54(h)(8) ]

[ (9) Multi-section units mating line column supports:]

[ (A) On multi-section units, openings larger than 4 feet must have piers installed at each end of the opening. To determine the pier loads, refer to Table 3D in subparagraph (D) of this paragraph.]

[ Figure: 10 TAC §80.54(h)(9)(A) ]

[ (B) Column loads for each section may be combined when the columns are opposite each other. The footer must be sized for the combined loading.]

[ (C) Additional piers are required under marriage walls (see wall between column #3 and #4 in the Marriage Line Elevation drawing in subparagraph (A) of this paragraph). The maximum spacing is the same as the spacing at the main I-Beams, without perimeter piers, and one half the spacing of the perimeter piers, with perimeter piers installed.]

[ (D) Table 3D: Mating line column loads (pounds).]

[ Figure: 10 TAC §80.54(h)(9)(D) ]

§80.55. Generic Standards for Anchoring Systems.

(a) General Requirements: For units built on or after September 1, 1997, the installer must verify that the unit is designed for the Wind Zone in which it is to be installed and must follow all applicable installation instructions for that Wind Zone as set forth herein. See figure in §80.240(b)(1) of this title for counties located in Wind Zone II. Note: A Wind Zone I unit, built on or after September 1, 1997, may not be installed in a Wind Zone II area. However, a Wind Zone II unit may be installed in a Wind Zone I area.

[ Figure: 10 TAC §80.55(a) ]

(b) Material Specifications:

(1) Strapping shall be Type 1, Finish B, Grade 1 steel strapping, 1.25 inches wide and 0.035 inches in thickness, certified by a licensed professional engineer or architect as conforming with the American Society for Testing and Materials (ASTM) Standard Specification D3953 91, Standard Specification for Strapping, Flat Steel, and Seals. [ Tie materials shall be capable of resisting an allowable working load of 3,150 pounds with no more than 2% elongating and shall withstand a 50% overload (4,725 pounds total). Ties shall have a resistance to weather deterioration at least equivalent to that provided by coating of zinc on steel of not less than 0.30 ounces per square foot on each side of the surface coated (0.0005 inches thick), as determined by ASTM Standards Methods of Test for Weight of Coating on Zinc-coated (galvanized) Iron or Steel Articles (ASTM A 90-81). Slit or cut edges of zinc-coated steel strapping are not required to be zinc coated. ] Strapping shall be marked at least every five feet with the marking described by the certifying engineer or architect.

(2) Tie materials shall be capable of resisting an allowable working load of 3,150 pounds with no more than 2% elongating and shall withstand a 50% overload (4,725 pounds total). Ties shall have a resistance to weather deterioration at least equivalent to that provided by coating of zinc on steel of not less than 0.30 ounces per square foot on each side of the surface coated (0.0005 inches thick), as determined by ASTM Standards Methods of Test for Weight of Coating on Zinc-coated (galvanized) Iron or Steel Articles (ASTM A 90-81). Slit or cut edges of zinc-coated steel strapping are not required to be zinc coated. Ties shall be designed and installed to prevent self disconnection when the ties are slack. For example, open end hooks shall have set screws or other mechanisms to prevent disconnection when there is slack in the strapping. [ All anchoring components must be approved by the department. Installers shall only use approved anchoring components. An installer may obtain a list of approved anchoring components from the department, anchor manufacturer and/or supplier of anchoring components. ]

(3) Anchor spacing ONLY applies to units with roof pitch of 20 degrees or less. For anything over 20 degrees, it must be designed by a professional engineer or architect.

(c) Anchors shall be installed per the figures in §80.240(b)(2) and (3) of this title. [ following details: ]

(1) in direction of load, see the Anchor Installation figure in §80.240(b)(2) of this title.

[ Figure: 10 TAC §80.55(c)(1) ]

(2) installed against direction of load (vertical and/or angled), a stabilizer plate must be installed. See Placement of Stabilizing Plates figure in §80.240(b)(3) of this title.

[ Figure: 10 TAC §80.55(c)(2) ]

(d) WIND ZONE I Installation:

(1) See the Wind Zone I Installation figure in §80.240(b)(4) of this title for the typical [ Typical ] anchor layout, single and multi-section units (WIND ZONE I ONLY) . [ : ]

[ Figure: 10 TAC §80.55(d)(1) ]

(2) [ Table 4A: ]The [ following ] table in §80.240(a)(1) of this title describes the maximum spacing for diagonal ties along each side of the unit.

[ Figure: 10 TAC §80.55(d)(2) ]

(3) The table in §80.240(a)(2) of this title describes the minimum [ Table 4B: Minimum ] number of diagonal ties required per side, per unit length. Table based on 2 feet inset of anchors at each end.

[ Figure: 10 TAC §80.55(d)(3) ]

(4) When [ approved ] auger anchors cannot be inserted into a difficult soil after moistening, such as mixed soil and rock or caliche (heavily weathered limestone) that is not solid rock, [ approved ] cross drive rock anchors may be used in accordance with the values and notes for the table in §80.240(a)(1) of this title [ Table 4A in paragraph (2) of this subsection ] modified as follows:

(A) Since the ultimate anchor pull out in the difficult soil will be reduced, the maximum spacing for diagonal ties per side is one half the spacing allowed by the table in §80.240(a)(1) of this title [ Table 4A ] which will require adding one additional cross drive rock anchor for each anchor specified for the sides and ends;

(B) The rods of the [ approved ] cross drive rock anchors must be fully inserted, have at least 24 inches of the rod lengths embedded in the difficult soil, and be restrained from horizontal movement, when feasible, by a stabilizer plate between the rods and the home; and

(C) Each cross drive rock anchor is connected to one diagonal tie and is not connected to a vertical tie.

(e) WIND ZONE II Installation:

(1) In place of the requirements as shown in subsection (d) of this section, units designed for Wind Zone I and built prior to September 1, 1997, and units designed for Wind Zone II and built prior to July 13, 1994, require diagonal ties as set forth in the table in §80.240(a)(3) of this title [ Table 5A ] when these units are installed in Wind Zone II. See also §1201.256 of the Standards Act [ §80.50 of this title (relating to Wind Zone Regulations) ]. Items not specifically addressed in this section are the same as for Wind Zone I installations.

[ Figure: 10 TAC §80.55(e)(1) ]

(2) Units built to Wind Zone II on or after July 13, 1994.

(A) Units built to Wind Zone II on or after July 13, 1994, should have either built-in, or provisions for connecting, vertical ties along the sidewall(s) of each unit(s). A diagonal tie must be installed at each vertical tie location (except for designated shearwall tie). Built-in vertical ties shall be connected to anchors. If there are brackets or other provisions for connecting vertical ties, vertical ties shall be added at the brackets or provisions and connected to anchors.

(B) Only factory installed vertical ties may be closer than 4 feet from each other.

(C) Where tie locations are clearly marked as a shear wall strap, a perimeter pier must be installed at that location. [ See subsection §80.54(d) of this title (relating to Standards for the Installation of Manufactured Homes) for perimeter pier construction. ] Diagonal tie is not required.

(D) Where the vertical tie spacing exceeds 8'-0" on-center (see also note 6 in the table in §80.240(a)(3) of this title [ table 5A ] for exception), the anchoring system must be approved by the home manufacturer's installation manual, or designed by a professional engineer or architect licensed in the state of Texas.

(E) Where pier heights exceed 36 inches in height, the diagonal strap shall be connected to the opposite I-Beam [ (see Figure 1) ]. See the Diagonal Strap Placement for Piers Exceeding 36 inches in Height figure in §80.240(b)(5) of this title.

[ Figure: 10 TAC §80.55(e)(2)(E) ]

(F) Where vertical tie locations are not easily discernable, the vertical ties may be connected to the main I-Beam rails and the anchor installed directly below that connection point. The diagonal tie must be connected to the opposite main I-Beam. In no case shall the distance between those ties exceed 5'-4" on-center [ (see Figure 2) ]. See the Diagonal and Vertical Ties figure in §80.240(b)(6) of this title.

[ Figure: 10 TAC §80.55(e)(2)(F) ]

(3) Multi-section centerline anchoring requirements (Wind Zone II only):

(A) Centerline anchor ties are required for ALL Wind Zone II installations, regardless of the date the unit was manufactured, when installation occurs on or after the effective date of these rules.

(B) Factory installed centerline vertical ties, brackets, buckles or any other connecting devices must be connected to a ground anchor. No additional anchors as described in subparagraph (D) of this paragraph are required.

(C) To avoid obstructions and/or piers and footers, the anchor may be offset up to 12 inches perpendicular to the centerline.

(D) Where factory preparations do not exist, install anchors and angle iron brackets at each side of mating line openings wider than 48 inches per the table in §80.240(a)(4) of this title [ table 5B (see Figure 5B for detail) ]. See the Typical Installation Details figure in §80.240(b)(7) of this title for detail.

(i) Where equal spans exist opposite each other (i.e., each section), a double bracket assembly may be used. The maximum opening is per the table in §80.240(a)(4) of this title [ table 5B ]. Total uplift load may not exceed the anchor and/or strap capacity (i.e., 3150 pounds).

(ii) The angle iron bracket is minimum 11 gauge. The holes for the lag screws are a maximum of 4 inches apart.

(iii) Lag screws/bolts are minimum 5/16 x 3 inches, full thread.

(4) For openings separated by a wall or post 16 inches or less in width, the opening span is the total of the spans on each side of the wall/post.

(f) Bracket Installation.

(1) See the table in §80.240(a)(4) of this title concerning the maximum centerline [ Table 5B: Maximum Centerline ] wall opening for column uplift brackets (see §80.240(b)(7) of this title [ figure 5B ] for typical installation details).

[ Figure: 10 TAC §80.55(f)(1) ]

(2) Section 80.240(b)(7) of this title [ Figure 5B ] shows both single and double bracket assemblies for illustration purposes only. Use a single bracket for openings which exist on one section only. Use double bracket where openings are opposite each other on two sections of the home.

(3) When only one bracket assembly is required, it may be installed on either side of the column/opening stud(s), but no more than 12 inches from the column or opening stud(s). See the Anchor Span figure in §80.240(b)(8) of this title for examples. [ (See examples in figure 5C.) ]

(4) When two bracket assemblies are required, they must be installed on each side of the column/opening stud(s), but no more than 12 inches from the column/opening stud(s) [ (see examples in figure 5C) ], and they must be angled away from each other a minimum of 12 inches. See the Anchor Span figure in §80.240(b)(8) of this title for examples.

[ Figure: 10 TAC §80.55(f)(4) ]

(5) Example: A double section unit with each section being 14 feet wide;

(A) Span "A" is 18'-0", matching span both sections;

(B) Span "B" is 14'-8", matching span both sections;

(C) Span "C" is 6'-8", matching span both sections; and

(D) Span "D" is 13'-4", one side only. (See the Anchor Span figure in §80.240(b)(8) of this title.)

[ Figure: 10 TAC §80.55(f)(5)(D) ]

(6) Longitudinal ties:

(A) Longitudinal ties are required for ALL wind zone installations, regardless of the date of manufacture, when installation occurs after the effective date of these rules.

(B) Longitudinal ties are designed to prevent lateral movement along the length of the home.

(C) When conventional anchors and straps are used, install the required number of ties per the table in §80.240(a)(1) of this title [ Table 4A ] or the table in §80.240(a)(3) of this title [ Table 5A ] as appropriate. The strap(s) may be connected or wrapped around front or rear chassis header members, around existing cross members or spring hangers. A strap must be within 3 inches of where the cross member attaches to the main I-beam. Alternatively, brackets to receive the strap(s) may be welded to the bottom flange of the main I-beams. The location of the connection points along the length of the I-beams are not critical, as long as the number of longitudinal ties required for each end of each home section are installed with their pull in opposite directions. No two anchors shall be within 4 ft of each other. No two ties shall be attached to the same structural member of the home, other than a main longitudinal frame member or a front or rear chassis header member.

(D) Anchors require stabilizer plates when the anchor shaft is not in line with strap (plus or minus 10 degrees).

[ Figure: 10 TAC §80.55(f)(6)(D) ]

§80.56. Generic Standards for Multi-Section Connections [ Connection ] Standards.

(a) Air infiltration and water vapor migration at mating surfaces: Before positioning additional sections, the mating line surfaces along the floor, endwall and ceiling, require material or procedures to limit air infiltration and water vapor migration. See the Mating Line Surfaces figure in §80.240(b)(11) of this title. The following are acceptable materials and/or procedures:

(1) Expanding Foam: Foam may be used along surfaces that are accessible after the units have been joined. Where mating line walls line up between sections, non-porous materials must be installed prior to joining the units.

(2) Caulking: Caulking may be used along surfaces that are accessible after the units have been joined. Where mating line walls line up between sections, non-porous materials must be installed prior to joining the units.

(3) Non-porous gasket installed along the perimeter of all mating lines.

(4) Insulation, carpet, carpet pad or other porous materials are not acceptable.

[ Figure: 10 TAC §80.56(a)(4) ]

(b) Floor Connections:

(1) Gaps between floors up to 1-1/2 inches maximum which do not extend the full length of the floor may be filled with lumber, plywood or other suitable shimming materials. Fastener lengths in shimmed areas may need to be increased to provide minimum 1-1/4 inches penetration into opposite floor rim joist.

(2) Gaps less than 1/2 inch width need not be shimmed.

(3) The floor assemblies of multi-section units must be fastened together. Fastener options and maximum spacings are listed in the floor connections table in §80.240(a)(5) of this title [ table 6A in paragraph (5) of this subsection ].

(4) Any tears or damages to the bottom board due to fastener installation must be repaired.

(5) See the floor connections table in §80.240(a)(5) of this title. [ Table 6A: Floor connections - Wind Zone I and II: ]

[ Figure: 10 TAC §80.56(b)(5) ]

(c) Endwall Connections:

(1) Endwalls must be fastened together at the mating line with minimum #8x4 inch wood screws or 16d nails at maximum 8 inches on-center or 12 inches on-center maximum for 5/16 lags; toed or driven straight; and

(2) Fastener length may need to be adjusted for gaps and/or toeing, to provide minimum 1-1/2 inch penetration into opposite endwall stud.

[ Figure: 10 TAC §80.56(c)(2) ]

(d) Roof Connection: (Note: Fasteners must not be used to pull the sections together.)

(1) Roof shall be connected with the fasteners and spacings specified in the table in §80.240(a)(6) of this title [ Table 56(d)(3) ].

(2) Gaps between the roof sections (at ridge beam and/or open beam ledgers) of up to 1-1/2 inches wide maximum which do not extend the full length of the roof must be filled with lumber and/or plywood shims. Gaps up to 1/2 inch need not be shimmed. The fastener length used in the shimmed area may need to be increased to provide a minimum 1-1/4 inch penetration into the adjacent roof structural member.

(3) See the roof connections table in §80.240(a)(6) of this title. [ Table 56(d)(3): Roof Connection - Fastener type and spacing: ]

[ Figure: 10 TAC §80.56(d)(3) ]

(4) See the Roof Connection figure in §80.240(b)(14) of this title [ Figure 56(d)(4) ].

[ Figure: 10 TAC §80.56(d)(4) ]

(e) Exterior Roof Close Up (see the figure in §80.240(b)(15) of this title) :

(1) Ensure that shingles are installed to edge of roof decking at peak. Follow nailing instructions on the shingle wrapper. Note: Wind Zone II (high wind) installations require additional fasteners.

(2) Before installing ridge cap shingles, a minimum 6 inch wide piece of 30 gauge galvanized flashing must be installed the length of the roof.

(3) When flashing is not continuous, lap individual pieces a minimum of 6 inches.

(4) Fasten flashing into roof sheathing with minimum 16 gauge staples with 1 inch crown or roofing nails of sufficient length to penetrate roof decking. Maximum fastener spacing is 6 inches on-center each roof section. Place fasteners a minimum of 3/4 inches along edge of flashing.

(5) Install ridge shingles directly on top of flashing.

(6) Check remainder of roof for any damaged or lose shingles, remove any shipping plastic or netting, wind deflectors, etc. Make sure to seal any fastener holes with roofing cement.

[ Figure: 10 TAC §80.56(e)(6) ]

(f) Exterior Endwall Close Up: Cut closure material to the shape and size required and secure in place, starting from the bottom up, type-name="italic">i.e.: [ i.e.: ] bottom starter, vertical or horizontal siding, then roof overhang, soffit and fascia. All closure material should be fitted and sealed as required to protect the structure or interior from the elements.

(g) HVAC (heat/cooling) Duct Crossover (see the figure in §80.240(b)(16) of this title) :

(1) Crossover duct must be listed for EXTERIOR use.

(2) Duct R-value shall be a minimum of R-4.

(3) The duct must be supported 48 inches on-center (maximum) and must not be allowed to touch the ground. Either strapping (minimum 1 inch wide) , to hang the duct from the floor, or non-continuous pads to support it off the ground are acceptable.

(4) The duct to the collar or plenum connections must be secured with bands or straps designed [ approved ] for such use. Keep duct as straight as possible to avoid kinks or bends that may restrict the airflow. Extra length must be cut off.

[ Figure: 10 TAC §80.56(g)(4) ]

(h) Multi-Section Water Crossover Connection (see figure in §80.240(b)(17) of this title [ (multi-sections only) ]:

(1) If there is water service to other sections, connect the water supply crossover lines as shown in the applicable detail.

[ Figure: 10 TAC §80.56(h)(1) ]

(2) If the water crossover connection is not within the insulated floor envelopes, wrap the exposed water lines in insulation and secure with a good pressure sensitive tape or nonabrasive strap, or enclose the exposed portion with an insulated box.

(3) If water piping at the inlet is exposed, a heat tape should be installed to prevent freezing. A heat tape receptacle has been provided near the water inlet. When purchasing a heat tape, it must be listed for manufactured home use, and it must be installed per manufacturer's instructions.

(i) Drain, Waste and Vent System (DWV):

(1) Portions of the DWV system which are below the floor may not have been installed, to prevent damage to the piping during transport. Typically, the DWV layout is designed to terminate at a single connection point to connect to the on-site sewer system. For a new home where on-site DWV connections are not assembled per the manufacturer's instructions, the DWV system must be assembled in accordance with Part 3280 of the FMHCSS. See the Drain, Waste and Vent Floor Piping System figure in §80.240(b)(18) of this title.

(2) The following guidelines apply:

(A) All portions of the DWV system shall be installed to provide a minimum of 1/4 inch slope per foot, in the direction of the flow.

(B) Changes in direction from vertical to horizontal, and horizontal to horizontal, shall be made using long sweep elbows and/or tees.

(C) All drain piping shall be supported at intervals not to exceed 4 feet on-center. The support may be either blocking or strapping. When strapping is used, it should be nonabrasive.

(D) Piping must be assembled with the appropriate cleaners, primers and solvents (note: both ABS and PVC systems are common, but require different adhesives). Be sure to follow the instructions of the product used.

(E) A cleanout must be installed at the upper (most remote) end of the floor piping system (see diagrams in the Drain, Waste and Vent Floor Piping System figure in §80.240(b)(18) of this title [ subparagraph (F) in this paragraph ]).

[ (F) Typical details: ]

[ Figure: 10 TAC §80.56(i)(2)(F) ]

(j) Electrical Connections: Depending on the model and/or manufacturer of the home, electrical crossovers may be located in either the front end and/or rear end of the home. Check along mating line for other labeled access panels.

(1) Crossover connections may be one of the following:

(A) [ approved ] snap or plug-in type;

(B) junction boxes inside floor cavity (note: crossover wiring routed outside the floor cavity must be enclosed in conduit). If the boxes and/or covers are metal, they must be grounded by the use of the ground wire; or

(C) pigtail between receptacles/switches between sections (one circuit only).

(2) Chassis Bonding: Each chassis shall be bonded to the adjacent chassis with a solid or stranded, green insulated or bare, number 8 copper conductor. The conductor is connected to the steel chassis with a solderless lug. See the Chassis Bonding figure in §80.240(b)(19) of this title. Alternate bonding: A 4 inch wide by 30 gauge continuous metal strap may be used as an alternate, when attached to the chassis members with two #8x 3/4 inch self tapping metal screws each end of the strap. [ Alternate bonding: A 4 inch wide by 30 gauge continuous metal strap may be used as an alternate, when attached to the chassis members with two #8x 3/4 inch self tapping metal screws each end of the strap. ]

[ Figure: 10 TAC §80.56(j)(2) ]

(3) See the Electrical Crossover figure in §80.240(b)(20) of this title for typical crossover details . [ : ]

[ Figure: 10 TAC §80.56(j)(3) ]

(4) Shipped loose equipment:

(A) Electrical equipment such as ceiling fans, chandeliers, exterior lights, etc., which may have been shipped loose, must be installed in accordance with the adopted National Electric Code (NEC). Connect all corresponding color coded or otherwise marked conductors per the applicable sections of the NEC.

(B) Bonding strap removal: 240 volt appliances (range, dryer, etc.) shall have the bonding strap removed between the ground and the neutral conductors. Cords used to connect those appliances shall be four conductor, four prong.

(5) Electrical testing: At the time of installation, the following tests must be performed:

(A) All site installed or shipped loose fixtures shall be subjected to a polarity test to determine that the connections have been properly made.

(B) All grounding and bonding conductors installed or connected during the home installation shall be tested for continuity, and

(C) All electrical lights, equipment, ground fault circuit interrupters and appliances shall be subjected to an operational test to demonstrate that all equipment is connected and functioning properly.

(6) Main panel box feeder connection: The main panel box is wired with the grounding system separated from the neutral system (4-wire feeder). The grounding bus in the panel must be connected through a properly sized green colored insulated conductor to the service entrance equipment (meter base) located on or adjacent to the home. Refer to the [ following ] table in §80.240(a)(7) of this title for proper feeder conductor sizes.

[ Figure: 10 TAC §80.56(j)(6) ]

(k) Fuel Gas Piping Systems:

(1) Crossover Connections: All underfloor fuel gas pipe crossover connections shall be accessible and be made with the connectors supplied by the home manufacturer, or, if not available, with flexible connectors listed for exterior use and a listed quick disconnect (Method A), or a shut-off valve (Method B). When shut-off valve is used, it must be installed on the supply side of the gas piping system. The crossover connector must have a capacity rating (BTUH) of at least the total BTUH's of all appliances it serves.

(2) Testing: The fuel gas piping system shall be subjected to an air pressure test of no less than 6 ounces and no more than 8 ounces. While the gas piping system is pressurized with air, the appliance and crossover connections shall be tested for leakage with soapy water or bubble solution. This test is required of the person connecting the gas supply to the home, but may also be performed by the gas utility or supply company. See the Fuel Gas Pipe Crossover Connections figure in §80.240(b)(21) of this title.

[ Figure: 10 TAC §80.56(k)(2) ]

§80.57.Generic Standards for Moisture and Ground Vapor Controls.

(a) If the manufactured home is installed according to the state's generic standards and the space under the home is to be enclosed with skirting and/or other materials provided by the retailer and/or installer, an access opening not less than 18 inches in any dimension and not less than three square feet in area shall be provided by the installer. The access opening shall be located so that any water supply and sewer drain connections located under the home are accessible for inspections. If a clothes dryer exhaust duct, air conditioning condensation drain, or combustion air inlet is present, the installer must pass it through the skirting to the outside. In addition, crawl space ventilation must be provided at the rate of minimum 1 square foot of net free area, for every 150 square feet of floor area. At least six openings shall be provided, one at each end of the home and two on each side of the home. The openings shall be screened or otherwise covered to prevent entrance of rodents (note: screening will reduce net free area). For example, a 16'x76' single section home has 1216 square feet of floor area. This 1216 square feet divided by 150 equals 8.1 square feet or 1166 square inches of net free area crawl space ventilation.

(b) The retailer and/or installer must notify the purchaser that moisture and ground vapor control measures are required if the space under the home is to be enclosed. Water vapor build-up may cause dampness in the home, damage to siding and bottom board, buckling of walls and floors, delamination of floor decking and problems with the operation of windows and doors. The generic ground vapor control measure shall consist of a ground vapor retarder that is minimum 6 mil polyethylene sheeting or its equivalent, installed so that the area under the home is covered with sheeting and overlapped approximately 12 inches at all joints. Any tear larger than 18 inches long or wide must be taped using a material appropriate for the sheeting used. The laps should be weighted down to prevent movement. Any small tears and/or voids around construction (footings, anchor heads, etc.) are acceptable.

(c) Notice: The Site Preparation Notice form to be given to the consumer is located in §80.260(a)(1) of this title.

§80.58.Generic Standards for Footers and Piers.

(a) Proper sizing of footings depends on the load carrying capacity of both the piers and the soil. To determine the load bearing capacity of the soil, the installer may use any of the following methods:

(1) Pocket penetrometer:

(A) Test a typical area adjacent to or within 10 feet of the perimeter of the unit;

(B) Dig down to undisturbed soil. Each hole should be a minimum of 1 square foot surface area; and

(C) Using the pocket penetrometer take seven (7) readings, eliminate the highest and the lowest and average the remaining five (5).

(2) Soil surveys from the U.S. Department of Agriculture;

(3) Values from tables of allowable or presumptive bearing capacities given in local building codes. Such tables are commonly available from the local authority having jurisdiction; or

(4) Any other test data from soil analysis reports.

(b) The footing must be placed on firm, undisturbed soil, or fill compacted to at least 90% of its maximum relative density. Installation on loose, noncompacted fill may invalidate the home's limited warranty.

(c) See the Footer Configurations figure in §80.240(b)(22) of this title.

(d) Footer sizing and capacities: The Footer Capacities table in §80.240(a)(8) of this title represent maximum loads and spacings based on footer size and soil bearing capacity. Other footers may be used if equal or greater in bearing area than those footer sizes tabulated.

(e) Piers and pier spacings: One of the most important parts of home installation is proper pier installation. Incorrect size, location or spacing of piers may cause serious structural damage to the home. Spacing and location of piers shall be in accordance with the tables listed in §80.240(a)(9) and (10) of this title.

(1) Spacing shall be as even as practicable along each main I-Beam. Pier spacing may exceed tabulated values up to 30% so long as the total pier count remains the same. End piers are to be located within 24 inches of the end of the main frame.

(2) Piers shall extend at least 6 inches from the centerline of the I-Beam or be designed to prevent dislodgment due to horizontal movement of less than 4 inches.

(3) Load bearing supports or devices shall be registered with the department in accordance with §80.62 of this title (relating to Registration of Stabilizing Components and Systems).

(4) Sidewall openings greater than 4 feet shall have perimeter piers located under each side of the opening, i.e. patio doors, recessed porches/entries, bay windows and porch posts. Perimeter piers for openings are not required for endwalls.

(f) Pier design: Piers shall be constructed per the details in the Pier Design figure in §80.240(b)(23) of this title.

(1) Shimming (if needed): Shims are commonly used as a means for leveling the home and filling any voids left between the bottom flange of the I-Beam and the top of the pier cap. Wedge shaped shims must be installed from both sides of the I-Beam to provide a level bearing surface. The allowable height must not exceed 1 inch. Shims shall be a minimum of 3 inches wide and 6 inches long.

(2) See the table in §80.240(a)(9) of this title for the pier loads (pounds) at tabulated spacings WITHOUT perimeter supports.

(3) See the table in §80.240(a)(10) of this title for pier loads (pounds) at tabulated spacings WITH perimeter supports and the Perimeter Pier Front and Side View figure in §80.240(b)(24) of this title.

(g) See the Typical Multi-Section Pier Layout figure in §80.240(b)(25) of this title.

(h) See the Typical Single Section Pier Layout figure in §80.240(b)(26) of this title.

(i) Multi-section units mating line column supports:

(1) On multi-section units, openings larger than 4 feet must have piers installed at each end of the opening. To determine the pier loads, refer to the table in §80.240(a)(11) of this title. See the Determining Column Load and Marriage Line Elevation figure in §80.240(b)(27) of this title.

(2) Column loads for each section may be combined when the columns are opposite each other. The footer must be sized for the combined loading.

(3) Additional piers are required under marriage walls (see wall between column #3 and #4 in the Marriage Line Elevation figure in §80.240(b)(27) of this title. The maximum spacing is the same as the spacing at the main I-Beams, without perimeter piers, and one half the spacing of the perimeter piers, with perimeter piers installed.

(4) See the table in §80.240(a)(11) of this title for the mating line column loads.

§80.59.Exception to Generic Installation Standards.

When installing a manufactured home in accordance with the generic standards, installers must follow any applicable details of change set forth in this section as filed with the department in accordance with §80.53(g) of this title (relating to Requirements for Manufacturer's Designs and Installation Instructions).

(1) The Town & Country Homes' design requires a change to the standard set forth in §80.55(e)(2)(C) of this title (relating to Generic Standards for Anchoring Systems). All Town & Country Homes designed for 30#, 40#, and 60# roof loads or built with 2x6 exterior walls must have perimeter blocking.

(2) The Town & Country Homes' design requires a change to the standard set forth in §80.58(e)(4) of this title (Generic Standards for Footers and Piers). Town & Country Homes additionally require all exterior door locations to have perimeter piers.

(3) The Town & Country Homes' design requires a change to the standards set forth in §80.55(e)(2)(A) of this title (relating to Generic Standards for Anchoring Systems). All Town & Country Homes additionally require a pier and strap at the free end location of all interior shearwalls.

§80.62. Registration [ Approval ] of Stabilizing Components and Systems.

(a) Installers shall use only prefabricated or site built stabilizing components and systems which are:

(1) registered with the department,

(2) specified by the home manufacturer's DAPIA approved installation instructions, or

(3) specified for one or more homes in a particular area by a Texas licensed engineer or architect.

(b) [ (a) Installers shall use only prefabricated or site built stabilizing components and systems approved by the department, specified by the home manufacturer's DAPIA approved installation instructions, or specified for one or more homes in a particular area by a Texas licensed engineer or architect. ] Before accepting a registration of [ granting approval for ] any prefabricated stabilizing component or system that will be used for more than one home or granting renewal of such, the department will require the component or system to be certified by an engineer, architect, or independent testing laboratory. The engineer or architect may be licensed in any state. The independent testing laboratory must have at least one engineer or architect licensed in at least one state. The producer or vendor of the component or system [ seeking department approval ] must send a request letter to the department with at least two copies of the certification report. The department may accept certification reports in electronic formats. The certification report copies must have letter size (8.5 inch by 11 inch) or smaller pages. The [ In the request letter, the ] producer or vendor must provide written permission to [ grant ] the department [ the right ] to reproduce the certification report. If the department accepts the registration of [ approves ] the certification report, the department shall place a registration stamp [ of approval ] on the copies, keep one copy, and return all other stamped copies to the producer or vendor. The registration stamp [ of approval ] will include [ have ] the following information:

(1) the title "Texas Department of Housing and Community Affairs" Manufactured Housing Division ;

(2) the phrase " Registered [ Approved ] stabilizing component or system"; and

(3) the date of registration [ approval ].

(c) [ (b) ] The department will maintain a list of stabilizing components and systems that have been registered with [ approved by ] the department for use in Texas.

(d) [ (c) ] A report that certifies a stabilizing component or system shall contain, at the minimum, the following:

(1) the name, address, phone number, facsimile number, and trademark of the agency issuing the certification report or the name, signature, license number, state where licensed, address, phone number, facsimile number, and seal of the engineer or architect;

(2) date of certification report;

(3) the name, address, phone number, and facsimile number of the vendor or producer of the component or system;

(4) drawing or photograph of component or system;

(5) a description of the vendor's or producer's method for identifying the component or system;

(6) at least a 2 inch by 4 inch blank space for the department registration [ approval ] stamp on each page or the cover page of a bound document;

(7) a unique number or other identification for the certification report;

(8) the initial qualifying test report or information about how the report can be obtained;

(9) a description of the continuing validation system and the time period of the certification;

(10) installation instructions for the component or system that are shipped to each purchaser;

(11) a description of the working load capacity for the component or system. If the component is a ground anchor, the anchor shall be certified by a professional engineer, architect or nationally recognized testing laboratory as to its resistance, based on the maximum angle of diagonal tie and/or vertical tie loading and angle of anchor installation, and type of soil in which the anchor is to be installed;

(12) a description of all allowable conditions for use of the component or system such as (but not limited to) types of soil, weather exposure, atmospheric environment (rural, industrial, coastal), and characteristics of other associated components; and

(13) a statement that the certifying independent testing laboratory, certifying engineer, or certifying architect certifies the component or system to be in conformance with all applicable standards [ a specific standard ] adopted by the department. This statement shall be on each page or shall be on the cover sheet of a bound document.

(e) [ (d) ] The department adopts the applicable standards and publications set forth in Chapter 43 of the International Code Council, latest edition of the [ 2000 ] International Residential Code for materials used to fabricate stabilizing components and systems. The department adopts the stabilizing component destruction test failure criteria of the FMHCSS (24 CFR, Part 3280) or latest edition of [ and ] the [ 2000 ] International Residential Code, Appendix E.

(f) [ (e) ] Applicable reports of the following organizations are acceptable as certification reports: National Evaluation Service, Inc.; International Conference of Building Officials (ICBO) Evaluation Service, Inc.; Southern Building Code Congress International (SBCCI) Public Safety Testing and Evaluation Services, Inc.; Building Officials and Code Administrators International (BOCA) Evaluation Reports, Inc.; the International Code Council (ICC); or a successor of any of these organizations.

(g) [ (f) ] The department may deny registration [ withhold approval ] if the certification information:

(1) is incomplete;

(2) does not conform to the rules of the department;

(3) contradicts the qualifying tests; or

(4) has contradictory statements.

(h) [ (g) ] Conditions that may cause the executive director to issue an administrative order that withdraws registration [ approval (or a renewal of approval) ] from a stabilizing component or system may include but are not limited to:

(1) the engineer, architect, or independent testing laboratory withdraws the certification;

(2) the engineer, architect, or independent testing laboratory improperly certified the component or system;

(3) a significant characteristic of a device or system has been changed without a revision of the original certification;

(4) the producer distributes installation instructions that are substantively different from those in the certification or original qualifying tests;

(5) changes in the law, rules, or standards;

(6) the continuing validation system for a component has been changed without a revision of the original certification;

(7) information provided by the original certification is obsolete;

(8) the department receives evidence that the component or system often fails to anchor or support the home, or [ and ]

(9) the producer fails to provide test results after the department directs the producer to test the component or system. The test will be performed by a recognized independent testing laboratory under the observation of a qualified representative or designee of the department.

(i) [ (h) ] Notice of withdrawal of registration [ approval ] of a component or system must be given to the producer and to all licensed installers, retailers, and manufacturers [ all license holders ].

(j) [ (i) ] The department's registration of a [ approval letters for ] stabilizing component or system is [ components and systems are ] valid for a period of ten (10) years or for the time period of certification, whichever is less. The registration [ approval letter ] expires at the end of the shorter period.

(1) If the time period for certification exceeds the ten (10) year registration [ approval ] period, the producer of the stabilizing component or system [ components and systems ] may apply for a renewal of the registration [ approval letter ]. The renewal shall be valid for an additional period:

(A) of ten (10) years; or

(B) if the time period of certification expires prior to the end of the ten (10) year period, for a lesser period ending with the expiration of the time period of certification.

(2) All department approval letters issued prior to November 3, 1998, [ the effective date of this section ] remain valid for a period of ten (10) years [ and expire ten (10) years ] following the original effective date of this section and expire on November 3, 2008, or upon any previously assigned expiration date if that date is earlier .

(k) [ (j) ] A registration renewal request must be received from the [ The ] vendor or producer of the component or system [ must apply for a renewal letter ] at least ninety (90) calendar days prior to the date the certification or registration [ approval letter ] expires . The request must [ and ] supply the information necessary for the department to issue a registration renewal [ letter ]. [ The department may issue a temporary renewal letter for a period of not more than six (6) months in order to have time to review all the information submitted by a producer or vendor. The contents of a renewal letter issued by the department are as follows: ]

[ (1) conditions of the renewal with a description of the department approval stamp that will appear on the document shipped by the producer or vendor to purchasers;]

[ (2) a unique number or other identification for the renewal letter;]

[ (3) the name, address, phone and facsimile number of the producer or vendor of the device or system;]

[ (4) a description of the continuing validation system and the time period of the renewal;]

[ (5) a reference to the document (single sheet or bound document) attached to the renewal letter which is shipped to each purchaser by the producer or vendor which includes:]

[ (A) the name, address, phone and facsimile number of the vendor of the component or system;]

[ (B) a description of the vendor's method of marking the component or system;]

[ (C) drawing or photograph of component or system with a reference to the detailed drawing stamped by an engineer or architect;]

[ (D) installation instructions;]

[ (E) reference to the initial qualifying test report;]

[ (F) reference to a previous Texas approval letter;]

[ (G) at least a 2 inch by 4 inch blank space for the department approval stamp on each page or a cover page for a bound document;]

[ (H) description of method for identifying the soil for ground anchors and footings;]

[ (I) a description of the working load capacity for the component or system;]

[ (J) if the component is a ground anchor, a certification by a professional engineer, architect, or nationally recognized testing laboratory as to its resistance, based on the maximum angle of diagonal tie and/or vertical tie loading and angle of anchor installation, and type of soil in which the anchor is to be installed; and]

[ (K) a description of all allowable conditions for use of the component or system such as (but not limited to) types of soil, weather exposure, atmospheric environment (rural, industrial, coastal), and characteristics of other associated devices.]

(l) [ (k) ] Registered [ Approved ] components and systems sold to retailers or installers prior to the expiration of the applicable registration [ approval letter ] or renewal [ letter ] may be used and installed for a period of not more than ninety (90) calendar days following the date of expiration of their [ the ] approval , registration, or renewal [ letter ].

(m) [ (l) ] In December of each year, the department shall mail to all licensed installers, retailers, and manufacturers a list of all registered [ approved ] components and systems and the date on which the registration [ approval letter ] for each component or system expires.

(n) Advertisements and instructions may not express or imply that the component or system has department approval.

§80.64.Procedures for Alterations.

(a) No alteration shall be made by a retailer or installer without prior written approval of the department. A written request for any alteration approval shall be filed with the department, except for the alterations which are pre-approved as described in this section. Approval will be granted upon evidence that Federal standards are met. If the alteration is approved, the alteration shall be completed in accordance with the department's approval and any requirements made as a condition of the approval. Following completion of an approved alteration, the retailer shall notify the department in writing, and the department may accept the certification of the retailer that the alteration was made as approved. The department may inspect the home, as altered, to assure compliance with the applicable standards.

[ (1) If the alteration is not approved, the department will notify the retailer in writing of the reason for the denial. If additional information is necessary to complete the evaluation of the request for approval, the retailer shall furnish any additional information deemed necessary by the department.]

[ (2) If the alteration is approved, the alteration shall be completed in accordance with the department's approval and any requirements made as a condition of the approval. Following completion of an approved alteration, the retailer shall notify the department in writing, and the department may accept the certification of the retailer that the alteration was made as approved. The department may inspect the home, as altered, to assure compliance with the applicable standards.]

(b) The installation of self-contained or split system ("A" coil) comfort cooling equipment and devices shall not be considered an alteration, if the installation is performed by a person holding the appropriate license in accordance with [ the ] specific written instructions , including specified tonnage, provided by one of the following: [ of the manufacturer of the home as approved by the manufacturer's DAPIA, and if the specific equipment and devices used have been expressly approved by the manufacturer's DAPIA. ]

(1) the manufacturer of the home, as approved by the manufacturer's DAPIA;

(2) a licensed professional engineer; or

(3) a licensed air conditioning contractor.

[ (c) Other than as set forth in subsection (b) of this section, the installation of self-contained or split system ("A" coil) comfort cooling equipment and devices is an alteration and is pre-approved if done by a state licensed air conditioning contractor.]

(c) [ (d) ] If the sale of a home includes air conditioning, the selling retailer shall maintain in the sales file a copy of the installation instructions that were followed as well as a record of the name and license number of the air conditioning contractor which installed the air conditioning system.

§80.66.Rebuilding or Repairing a "Salvaged" Manufactured Home.

(a) Any home which has sustained sufficient damage to be declared salvage as defined in §1201.461 of the Standards Act, may be rebuilt/repaired for purposes of issuance of a manufactured Statement of Ownership and Location [ home document of title ] at the option of the department after inspection in accordance with department procedures. Notification in writing to the department at its Austin headquarter's office shall be required before rebuilding/repair begins.

(b) The rebuilder must:

(1) notify the department in writing ten (10) business [ working ] days before rebuilding (or monthly for continuous activity) and provide the following, if available:

(A) HUD or Texas Seal number;

(B) data plate and comfort cooling certificate information (applicable wind and roof load zones, manufacturer's name and address, home model, list of appliance models, home production date, thermal zones, transmission coefficients, furnace certification temperatures, and duct capacity for cooling);

(C) copy of salvage declaration report;

(D) description of damage;

(E) description of cause of damage (water, wind, impact, fire, etc.); and

(F) location of home during rebuilding.

(2) provide a plan for rebuilding, sealed by a licensed professional engineer, that contains the following:

(A) drawings and specifications that describe the rebuilding;

(B) if more than one home is rebuilt in any one (1) month period, then a quality assurance manual that describes the following:

(i) system testing;

(ii) inspection process of cavities before concealment; and

(iii) record keeping.

(C) list of new parts and appliances;

(D) list of reused or salvaged parts and appliances; and

(E) rebuilder's data plate (if applicable).

(3) notify the department when concealed cavities will be exposed for department inspectors;

(4) remove damaged material and equipment;

(5) add new or used materials and equipment;

(6) repair all defects; and

(7) repair and test all systems.

(c) The department may schedule inspections of the home during the rebuilding process.

[ (d) Any person who purchased a rebuilt manufactured home and received a salvage title as evidence of ownership after June 18, 1987, may be issued a document of title upon application to the department.]

(d) [ (e) ] A manufactured home which has not sustained sufficient damage to be declared salvage may be refurbished to its original structural configuration so that it is habitable as defined by §1201.453 of the Standards Act.

This agency hereby certifies that the proposal has been reviewed by legal counsel and found to be within the agency's legal authority to adopt.

Filed with the Office of the Secretary of State on February 14, 2005.

TRD-200500651

Timothy K. Irvine

Executive Director, Manufactured Housing Division

Texas Department of Housing and Community Affairs

Earliest possible date of adoption: March 27, 2005

For further information, please call: (512) 475-2206


Subchapter E. GENERAL REQUIREMENTS

10 TAC §§80.119 - 80.133, 80.135

The new and amended sections are proposed under the Texas Manufactured Housing Standards Act, Occupations Code, Subtitle C, Chapter 1201, §1201.052, which provides the Department with authority to amend, add, and repeal rules governing the Manufactured Housing Division of the Department and under Texas Government Code, Chapter 2306, §2306.603, which authorizes the director to adopt rules as necessary to administer and enforce the manufactured housing program through the Manufactured Housing Division.

No other statute, code, or article is affected by the proposed new and amended rules.

§80.119.Installation Responsibilities.

(a) For new manufactured homes, the retailer is the installer and must certify [ warrant ] the proper installation of the home. If the retailer subcontracts with an independent licensed installer, then the subcontractor is jointly and severally liable for the portion of the installation that the subcontractor performed.

(b) For used manufactured homes, the person contracting with the consumer for the installation of the home is the installer and must certify [ warrant ] the proper installation of the home. If the contracting installer subcontracts with an independent licensed installer, then the subcontractor is jointly and severally liable for the portion of the installation that the subcontractor performed. The contracting installer is responsible to furnish the consumer with a written certification [ the installation warranty ] and site preparation notice. All verification and copies of the written certification [ installation warranty ] and site preparation notice must be maintained in the installer's installation file for a period of no fewer than six (6) years from the date of installation.

(1) The person contracting directly with the consumer for only the transportation of the used home to a manufactured home site is not an installer if the person does not perform or contract to perform any installation functions. In this case, the installer is the person that contracts for the construction of the stabilization [ foundation ] systems, whether temporary or permanent, and the placement and erection of the used home and its components on the stabilization [ foundation ] system.

(2) The selling retailer may sell a used home and deliver possession to the consumer at the sales location ( e.g. [ e.g. ], F.O.B. the sales location). In this case, the retailer shall not perform any installation functions nor transport the home to the home site.

(c) The installer is fully responsible for the complete installation in accordance with all applicable requirements set forth in this chapter even though the installer may subcontract certain installation functions to independent contractors pursuant to §1201.102(b) of the Standards Act. It is unlawful for a subcontractor who is acting as an agent for a licensed installer to advertise and/or offer installation services to any person unless the licensed installer's name appears prominently in the advertisement.

(d) The sale of a new or used home by a retailer which includes an agreement to deliver the home and install the home at the home site is complete when installation is complete and the home is made available [ not completed until possession of the home is tendered ] to the consumer for possession at the home site.

(e) The completed Notice of Installation (Form T) must be filed separately within thirty (30) days of the original sale or within ten (10) days of a secondary move.

(f) [ (e) ] Electrical, fuel, mechanical, and plumbing system crossover connections for multi-section homes, and completion [ completions ] of drain lines underneath all homes in accordance with the requirements of this chapter [ DAPIA approved on-site assembly drawings ] are installer responsibilities and cannot be excluded by wording of the installation contract. The installation of air conditioning at the home site must be performed by a licensed air conditioning contractor. The installation and ventilation of skirting or other material that encloses the crawl space underneath a manufactured home is an installer responsibility, if it is part of the sales or installation contract.

[ (f) For all secondary moves (where there is no title transfer) the Notice of Installation and the required fee must be submitted to the department within ten (10) working days after the installation is completed.]

[ (g) When the installer selects the department to inspect the permanent foundation before concealment, the installer shall file an application to install a manufactured home on a permanent foundation on a form approved by the department. The required fee for the permanent foundation installation report shall be forwarded with the application. After the department inspects the permanent foundation and indicates acceptance of the permanent foundation on the form, the title company, attorney, retailer, or retailer's agent later files the Notice of Installation, including a copy of the form, with the public land records of the county and forwards a copy to the department. The reporting fee does not have to be paid to the department again.]

[ (1) Unless the retailer/installer follows the home installation manual or a department pre-approved foundation systems, a copy of the foundation system drawing as stamped and signed by the licensed engineer or architect must be filed with the application.]

[ (2) The application must be received by the department at least ten (10) calendar days prior to the date on which construction of the permanent foundation system is scheduled to begin.]

[ (3) Installers shall provide a copy of the application and the foundation system drawing to the department inspector at the time an inspection is performed.]

[ (4) If the permanent foundation system design is approved by the authorized local government official and if the applicable building inspection fees are paid to the local government, the provisions of this section do not apply. The installer must, however, file a sworn statement of these facts with the Notice of Installation.]

[ (5) If the permanent foundation for a home acquired and installed before January 1, 2002 is certified by the consumer/mortgagor and the lender/mortgagee in a real estate transaction, or is certified by the owner if there is no lien or the lien has been released, as having permanently affixed the structure to the real estate, the provisions of this section do not apply. The installation reporting fee must be paid and sent to the department along with the certification.]

[ (6) When specifically requested in writing by the department with a Department Real Estate Inspection Request Form, a contracting local government shall make and perform inspection and enforcement activities related to the construction of the foundation that permanently affixes a manufactured home to real estate. If the permanent foundation system and other site improvements are inspected and accepted by a contracting local government official before concealment, the local government records may be the verification required by §1201.222(c) of the Standards Act. The retailer/installer must file a Notice of Installation, including a copy of the local government inspection report, with the public land records of the county and forward a copy of the Notice of Installation to the department with the reporting fee.]

[ (7) If the site suitability, site preparation, site improvement, foundation construction, and installation for a home acquired on or after January 1, 2002 are verified by a retailer or installer, the provisions of this section do not apply, but the title company, attorney, retailer, or retailer's agent must file a Notice of Installation with the public land records of the county and forward a copy of the Notice of Installation to the department with the reporting fee.]

§80.120.Manufacturer's Responsibilities.

Manufacturers licensed with the department shall:

(1) Submit a monthly shipment report to the department of all manufactured homes produced during the preceding month for shipment to any point in Texas. [ Submit the reports required by §80.203 of this title (relating to Manufacturer's Monthly Shipment Report); ]

(A) The report shall contain the following information:

(i) the complete HUD label number(s);

(ii) the complete serial number(s);

(iii) the license number of the retailer as assigned by the department;

(iv) a designation as to single or multiple sections; and

(v) the name and address of the purchaser, consignee, or person to whom it was shipped.

(B) The manufacturer's monthly shipment report shall be filed with the department by the 15th day of the month following the manufacture of the home and/or shipment.

(C) If a manufacturer has no sales, consignments, or shipments to any person or place during any month, the report must be filed stating such fact.

(2) Use the Manufacturer's Certificate of Origin (MCO) prescribed by the department for homes shipped to retailers in Texas; and

(3) Supply to the department current and revised copies of approved installation manuals as required by §80.53 [ §80.51 ] of this title (relating to [ Manufactured Home Installation ] Requirements for Manufacturer's Designs and Installation Instructions ).

§80.121.Retailer's Responsibilities.

(a) Manufactured housing retailers shall retain as part of each sales record and make available for copying and review by department personnel, upon request during normal business hours, the following information:

(1) For all manufactured homes as applicable :

(A) name and address of the purchaser and the date of purchase;

(B) verification that the purchaser received the Formaldehyde Health Notice required by §1201.153 of the Standards Act;

(C) verification that the purchaser was advised of the Wind Zone, thermal zone, and roof load zone for which the home was constructed. If this information is not available for a used home, the purchaser will be advised of this fact and the used home will be disclosed as being constructed to Wind Zone I, thermal zone 1, and the roof load design for the South;

(D) verification that the purchaser received the Wind Zone notice as required by §1201.256 of the Standards Act [ §80.50 of this title (relating to Wind Zone Regulations) ];

(E) verification that the purchaser received the site preparation notice;

(F) verification that the purchaser received written notice of the two (2) year limitation of notice for filing a claim with the department;

(G) verification that the Disclosure required in subsection (e) of this section [ by §80.181 of this title (relating to Section 162 Notice) ] was provided to the purchaser prior to completing a credit application;

(H) verification that the disclosure required in subsection (f) of this section [ by §80.182 (relating to 163 Disclosure) ] be delivered to the consumer at least 24 hours before execution of the contract in a chattel mortgage or consumer loan transaction;

(I) copies of the Notice of Installation (Form T) and attached documents;

(J) if the sale of a home includes air conditioning, the name and license number of the air conditioning contractor which installed the air conditioning system in accordance with §80.64 (c) [ (d) ] of this title (relating to Procedures for Alterations); [ and ]

(K) complete records of all alterations, in accordance with 24 CFR §3282.254 ; and [ . ]

(L) copies of the completed application and all supporting documentation as evidence that it conveyed good and marketable title to the manufactured home to the transferee. A contract to convey title after completion of an extended payout, as opposed to a financed extended payout secured by a lien on the manufactured home, does not constitute a conveyance of good and marketable title. An extended payout is any repayment involving more than one installment or any finance charge.

(2) For all new manufactured homes:

(A) verification that a copy or the general description of the manufacturer's new home warranty and installation warranty were given to the consumer prior to the retailer's signing of any binding retail installment sales contract or other mutually binding agreement.

(B) verification that the manufacturer's new home warranty, consumer's manual, and retailer's installation warranty were delivered to the purchaser pursuant to §1201.352(c) of the Standards Act (does not apply to damage caused by a move) ;

(C) verification of the date that the manufactured home information card was mailed to the manufacturer; and

[ (D) verification of delivery of conspicuous notice relating to defect or damage under the new home warranty as required by §1201.359(b) of the Standards Act.]

(3) For used manufactured homes:

(A) verification that the purchaser received the written 60-day habitability warranty; and

(B) if the retailer contracted for the installation as a part of the sales agreement, verification that a copy or the general description of the retailer's installation warranty was [ were ] given to the consumer prior to signing of any binding retail installment sales contract or other mutually binding agreement . [ , if the retailer contracted for the installation as a part of the sales agreement; and ]

[ (C) verification that the purchaser received the retailer's installation warranty if the retailer contracted for the installation as a part of the sales agreement.]

(b) All verifications and copies of notices required by this chapter must be maintained in the retailer's sales file, and the sales file must be maintained for a period of not less than six (6) years from the date of sale. If a retailer has more than one sales location and wishes to maintain all of its records at a central location, it may do so provided that the retailer notifies the department more than sixty (60) calendar days in advance that its records are being maintained at a central location by providing the address of such location. Absent such notice the records of a particular home must be maintained at the address where the home is in inventory and from which it was sold. If the retailer wishes to discontinue the centralization of its records or to change the address where its records are kept, the retailer must notify the department more than sixty (60) calendar days in advance of the change of the location and the address and effective date of the new location.

(c) For [ new homes or used ] homes manufactured on or after September 1, 1997, a manufactured housing license holder shall not contract for sale or installation of any home [ under which the home would be ] installed in a wind zone, thermal zone, or roof load zone other than that allowed on the data plate.

(d) In a joint purchase, one purchaser's signature is sufficient on the disclosure statement as long as the purchaser is on the loan documents.

(e) Section 162 Notice. Before accepting a completed credit application from a consumer, a retailer (or any salesperson or other agent acting on behalf of a retailer) shall provide the disclosure form in §80.260(a)(2) or (b)(1) of this title.

(1) The English version of Section 162 Notice form is located in §80.260(a)(2) of this title.

(2) The Spanish version of Section 162 Notice form is located in §80.260(b)(1) of this title. The retailer is not required to provide the form in Spanish; however, the consumer may request a copy in Spanish from the retailer or from the department.

(f) 163 Disclosure. In a chattel mortgage or consumer loan transaction in which the retailer is participating in anyway, the retailer shall deliver to the consumer, at least 24 hours before the execution of the contract, the disclosure form set forth in §80.260(a)(3) of this title and a copy of the contract to be executed with all information included, signed by the retailer.

(1) The English version of the 163 disclosure form is located in §80.260(a)(3) of this title.

(2) The Spanish version of the 163 disclosure form is located in §80.260(b)(2) of this title. The retailer is not required to provide the form in Spanish; however, the consumer may request a copy in Spanish from the retailer or from the department.

(3) The disclosure must be given in writing in at least 12 point type. It may not be attached to any other disclosure or document. The consumer must sign and date a copy of the disclosure to acknowledge that it was provided.

(g) A retailer may not represent to a consumer that is purchasing a manufactured home with interim financing that the consumer will qualify for permanent financing if the retailer has any reason to believe that the consumer will not qualify for such permanent financing.

(h) A retailer may not increase the advertised price or the agreed price at which a manufactured home is to be sold based on the consumer's decision to make the purchase with or without financing provided by or arranged through the retailer.

(i) If a retailer is also acting as a creditor or an arranger of credit and will receive compensation for such services, this must be disclosed to the consumer in writing.

(j) If a retailer is acting as a creditor or arranger of credit, the retailer may not require that a consumer obtain financing from or through them.

(k) If a retailer makes any material representation about a manufactured home that goes beyond the terms of written warranties to be provided, the retailer must confirm such representations in writing.

(l) If a retailer relies on a third party, such as a title company or closing attorney, to file with the Department the required forms necessary to enable the Department to issue a Statement of Ownership and Location to a consumer, the retailer must provide an instruction letter to that third party, advising them of their responsibilities to make such filings and the required timeframes therefore. The retailer must retain with their sale records a copy of that instruction letter and all documentation provided to such third party to enable them to make such filings.

(m) If a retailer, acting as a broker, negotiates the sale of a manufactured home that is not reflected on the records of the Department as being in the name of the seller, the retailer must disclose, in writing, the identity of the actual owner to any purchaser of such a home.

(n) If any goods or services being provided by a retailer in connection with the sale and/or installation of a manufactured home are to be provided at a date after the installation, the retailer must disclose, in writing, the goods and/or services to be provided and a good faith estimate as to when they will be provided.

(o) If any goods with a retail value of more than $250 are to be provided in connection with the sale of a manufactured home and they are not specified on the data plate for the home, the retailer must describe them in the retail installment contract, purchase memorandum, or other sale document in sufficient detail to enable a third party to provide them under the responsibility of the retailer's surety bond should the retailer fail to provide them as agreed.

(p) A retailer may not request or accept any document that is executed in blank or allow any alteration to a completed documented without the consumer's initialing and dating such changes to indicate agreement to them.

(q) A retailer may not knowingly accept or issue any check or other form of payment appearing on its face to be a bona fide payment but known not to represent good funds.

(r) A retailer accepting a deposit or down payment must give the consumer a written statement setting forth:

(1) The amount of such deposit or down payment;

(2) A statement whether the deposit or down payment is refundable or not and, if it is refundable, in whole or in part, a statement of any requirements to obtain or limitations on any such refund;

(3) The name and business address of the person receiving such down payment or deposit; and

(4) The HUD label number(s), Texas seal number(s), or serial number(s) of the manufactured home to which such down payment or deposit relates.

(s) A retailer may not negotiate or offer a refund of less than is required by the Act. However, a retailer may, by written agreement with the consumer retain the amount of the deposit used to pay legitimate third party costs actually incurred, such as credit report fees or courier fees.

(t) Prior to requiring a purchase to accept delivery of a manufactured home, the retailer must give them an opportunity to inspect the home to make sure that it conforms to their contract. When the purchaser signs a document acknowledging that the home which has been delivered conforms to their contract, the sale becomes final, but this in no way affects the operation of any warranty required by law or granted contractually or affects or abridges any rights or obligations of either of the parties to the transaction.

(u) On the sale of a used home, the retailer or broker must provide the purchaser with a disclosure advising the consumer either that they will be responsible for the installation (which will have a written warranty) or, if they will not be installing the home, a statement that they will not be installing the home and therefore will not be providing any warranty as to installation.

§80.122.Security Requirements.

(a) - (c) (No change.)

(d) To be exempt from the additional security as required by §1201.106(b) of the Standards Act, a manufacturer who does not have a manufacturing plant in this state must have a bona fide [ bona fide ] service facility.

(1) (No change.)

(2) The service facility shall be capable of compliance with the provisions of Sub-part I of the Manufactured Housing Improvement Act (latest edition) [ procedural and enforcement regulations promulgated by HUD, ] and capable of providing warranty service within the reasonable time requirements set by the department in §80.132 of this title (relating to Procedures for Handling Consumer Complaints) , and shall be subject to periodic review and inspection by department personnel.

(3) (No change.)

§80.123.License Requirements.

(a) - (b) (No change.)

(c) Broker.

(1) Any person engaged by one or more other persons to negotiate or offer to negotiate bargains or contracts for the sale, exchange, or lease purchase of a manufactured home to which a Statement of Ownership and Location [ certificate or document of title ] has been issued and is outstanding shall be licensed as a manufactured housing broker. An application for license shall be submitted on the form required by the department and be completed giving all the requested information. The application shall be accompanied by the required security, Articles of Incorporation or Assumed Name Certificate, and payment of the license fee. Each office location of the broker shall be licensed and proper security posted unless an office is on property which is contiguous to or located within 300 feet of an office licensed with the department.

(2) - (3) (No change.)

(d) - (e) (No change.)

(f) Homeowner's Temporary Installation.

(1) (No change.)

(2) The application must be accompanied by a certificate of insurance issued by the insurance carrier or its authorized agent to prove insurance coverage for the installation of the home as follows: public liability insurance coverage including completed operations in an amount of not less than $300,000 for bodily injury each occurrence and property damage insurance in an amount of not less than $100,000 each occurrence, for which a combined single limit of $300,000 will be considered to be in compliance with this section; and motor vehicle liability insurance coverage of not less than $250,000 bodily injury each person, $500,000 bodily injury each occurrence and $100,000 property damage each occurrence, for which a combined single limit of $500,000 will be considered to be in compliance with this section. [ A copy of the home manufacturer's installation instructions, custom designed installation instructions stamped by a Texas licensed professional engineer or architect, or an installation plan with details and specifications conforming to the state's generic standards shall accompany the application. ]

(3) - (4) (No change.)

(g) - (h) (No change.)

(i) Education Requirements. Effective September 1, 1987, all applicants for license[ , except salespersons, ] shall attend and complete 20 hours of educational instruction as required by the Standards Act and this chapter. A manufacturer may request a one-day in-plant training session be presented by the department in lieu of completing the instruction requirement. The license will not be issued until the owner, partner, corporate officer, or other person who will personally have the day-to-day management responsibility for the business location, or the salesperson to be licensed, attends and completes this educational requirement. Except as provided in §80.123(o) of this title (relating to License Requirements) , this section shall not apply to the renewal of licenses, nor to the license of additional business locations.

(j) - (n) (No change.)

(o) Continuing Education Requirements. For applications received on or after January 1, 2005, all persons engaged in sales of manufactured housing must be certified as having completed eight (8) hours of approved continuing education each year in order to renew any license as a retailer, broker, or salesperson or to apply for a new license as such when the person is so licensed or has been at any time in the preceding year.

(1) Covered persons. The following persons are deemed to be engaged in sales of manufactured housing and must meet the continuing education requirements [ and, therefore, must be certified as having completed eight (8) hours of approved continuing education each year in order to renew any license as a retailer, broker, or salesperson on or after January 1, 2005 ]:

(A) - (C) (No change.)

(2) Approval of courses and providers. In order to be considered for approval by the Board to provide continuing education courses a party wishing to be considered for such approval must submit, for each course for which approval is sought, a letter application, accompanied by a nonrefundable processing fee of $300, and the following:

(A) - (E) (No change.)

(F) Such other information as the department [ Department ] may require.

(3) Once the staff determines that a request for approval is complete, that request will be placed on the next regularly scheduled meeting of the board of Directors for consideration. The staff will provide the board with a written recommendation on each such request. The staff will advise the applicant of the board's action within ten (10) business [ working ] days of the date of the board meeting, including a written statement as to any limitations, conditions, or other requirements imposed.

(A) - (B) (No change.)

(4) Eight hours of approved training provided by the department will meet the continuing education requirement for license renewal. This may be in the form of attending eight hours of one of the department's quarterly licensing schools or by attending any other eight hour training class the department may offer. The department is under no obligation to offer any such classes (other than its regular quarterly licensing classes) and will do so only if it has sufficient resources to do so.

(p) Application and Appeals.

(1) Initial application processing.

(A) It is the policy of the department to issue the license within seven (7) business [ working ] days after receipt of all required information and the following conditions have been met:

(i) - (ii) (No change.)

(B) License applications and accompanying documents received shall be processed and issued within seven (7) business [ working ] days if all conditions for license have been met.

(C) License applications and accompanying documents found to be incomplete or not properly executed shall be returned to the applicant with an explanation of the specific reason and what information is required to complete license. Upon receipt of all required information, the license will be issued within seven (7) business [ working ] days.

(D) (No change.)

(2) (No change.)

(q) Payment of license fees.

(1) All required fees must be paid in order to obtain a valid license, including a renewal license, from the department.

(2) Any license issued by the department is void and of no effect if based upon a check that is later returned for insufficient funds, closed account, or other reason, regardless of whether the department notifies the applicant of the insufficiency of payment or the invalidity of the license.

(3) It is the applicant's responsibility to ensure that all licensing fees are paid in valid U.S. funds.

§80.124.Deposits and Down Payments.

(a) - (j) (No change.)

(k) Advancement/upgrade charges are not refundable if consumer agrees to reimburse retailer. If the consumer does not reimburse, the retailer has the right to deduct fees from the deposit amount.

§80.125.Advertising Regulations.

(a) - (b) (No change.)

(c) Any advertisement must comply with applicable federal laws. [ A retailer or broker must not advertise any interest rate or finance charge which is not expressed as an annual percentage rate and must comply with the disclosure requirements of the federal Truth-in-Lending Act. ]

(d) Any advertisement by a retailer, broker, salesperson, or installer (other than a sign/display advertisement at a licensed location, point of sale literature, or a price tag) must disclose the license number of the person who is advertising. If the person who is advertising is a salesperson, the advertisement must also indicate the license number of the retailer or broker on whose behalf the salesperson is advertising. The director may approve exceptions to the requirements of this subsection where no consumer protection purposes would be served by requiring the number to be disclosed.

§80.126.Rules for Hearings.

(a) - (d) (No change.)

(e) Pursuant to the Administrative Procedures Act, each party has the right to file exceptions to the Proposal for Decision and present a brief with respect to the exceptions. All exceptions must be filed with the department within ten (10) business [ working ] days of the Proposal for Decision, with replies to be filed ten (10) business [ working ] days after the filing of exceptions.

(f) When an administrative hearing is held for any matter in which the department [ Department ] seeks to take action against a licensee for violating the Standards Act or these rules, whether such action is an action to assess administrative penalties, to require corrective action, to require cessation of improper activities, to suspend or revoke a license, or any combination thereof, the department [ Department ] shall assess the costs of the proceeding against any party that fails to appear at a duly noticed administrative hearing. The costs assessed shall be the greater of $100 or the actual costs charged to the department [ Department ] by the State Office of Administrative Hearings, the Office of the Attorney General, any court reporter, or any other third party providing services in connection with such hearing.

(g) The department [ Department ] will seek the recovery of its costs from any party against whom it initiates an action if that action results in the entry of a final order taking any administrative action against that party, including the assessment of administrative penalties, requiring corrective action, requiring cessation of improper activities, suspension or revocation of a license, or any combination thereof.

§80.127.Sanctions and Penalties.

(a) - (c) (No change.)

(d) When a licensee first receives written notification of a claim for warranty service, the licensee must respond timely to the request. A failure to do so shall constitute a violation of these rules.

(1) It is presumed that a response was timely if the required warranty service is provided within forty (40) calendar days from the date of the request; provided, however, immediate corrective action is required [ that ] if the matter involves an imminent safety hazard[ , it must be addressed as quickly as is reasonably possible ].

(2) (No change.)

(3) If, after reasonable investigation, the licensee disputes whether warranty service is required and the licensee is unable to resolve the matter by agreement with the consumer, the licensee may request that the department [ Department ] perform an inspection of the home. The running of the time to respond to the request for warranty service will be suspended from the time the request for inspection is received until the department [ Department ] performs the inspection and issues its findings. When the department [ Department ] concludes its review it will work with the affected licensee(s) and consumer(s) to agree upon a reasonable time to address its findings. In the event the parties cannot agree on a reasonable time, the Director shall issue a revised order assigning a time for compliance. Any such order shall be subject to appeal and a hearing. Any such hearing shall be a contested case under Tex.Gov.Code, Chapter 2001.

(e) - (f) (No change.)

(g) When the department has reason to believe that a violation of the Standards Act, these Rules, or an administrative order has occurred, the department shall determine what, if any, administrative action or actions may be appropriate to see that the purposes of the Standards Act are carried out. In that regard, in order to promote the uniform application of the Standards Act, the department will follow these guidelines. The only time that the department will deviate from these guidelines is when either the Director or the Board determines, for documented bona fide reasons, that some other course of action, consistent with the Standards Act and any other applicable legal requirements would be more appropriate.

(h) As used herein, "dangerous conditions" means any condition which, if present, would constitute an imminent threat to health or safety, and "loss" means actual financial loss or damage, not including exemplary, punitive, special, or consequential damages. "Significant" means significant in relationship to the financial resources of the person who incurs a loss. "Promptly" means within the time prescribed by the Standards Act, these Rules, and any administrative order (including any properly granted extension) or, in the case of a matter that constitutes an imminent threat to health or safety, as quickly as reasonably possible.

(i) Any exceptionally flagrant, willful violation that constitutes an imminent threat to health or safety may be a basis for pursuit of maximum statutory penalties and/or suspension or revocation of licenses.

(j) Anytime the record indicates that there is a high likelihood that a licensee's violation is a direct result of a systemic problem, it is appropriate to request the licensee to develop a plan to prevent future occurrences. Undertaking to develop such a system is an appropriate factor to be taken into account in determining what penalty to pursue.

(k) Any and all penalties are IN ADDITION to full compliance with the Standards Act and Rules ( i.e. , full, prompt corrective action, restitution, or whatever else the Standards Act and rules would have required in the first place). Failure to provide such compliance on a timely basis, as specified in the applicable order, will be deemed to be a violation of the order and serve as a basis for pursuing additional administrative action, including the assessing of additional penalties and the pursuit of suspension or revocation of licenses.

(l) In determining the appropriate amount of a penalty or other action, all relevant factors shall be considered, including, but not limited to: the resources of the licensee and their ability to pay fines, efforts to achieve compliance, the nature and frequency of recurring violations, and monetary impact on consumers.

(m) The Enforcement Matrix is located in §80.240(a)(12) of this title.

§80.128.Arbitration Rules.

(a) - (i) (No change.)

(j) Arbitration Using SOAH. The provisions of this subsection relate only to arbitrations for which the parties have agreed to use the services of SOAH. Subject to the provisions of subsections (a) - (h) of this section, the parties shall follow these additional rules.

(1) - (4) (No change.)

(5) Filing and Service of Documents.

(A) - (B) (No change.)

(C) If any document is sent to the SOAH clerk by certified mail or first class mail in an envelope or wrapper properly addressed and stamped and is deposited in the mail on or before the last day for filing same, and it is received within three (3) business [ working ] days of the filing date, it shall be deemed properly filed.

(D) (No change.)

(6) - (26) (No change.)

§80.129.Alternative Dispute Resolution.

The department offers alternative dispute resolution as an inexpensive and informal way of attempting to resolve any claim or dispute. Depending on the parties, this may involve informal meetings or non-binding mediation. Alternative dispute resolution is available upon request. In the event that a disputed matter cannot be resolved in this manner, the department reserves the right to pursue all other lawful means of resolution including, but not limited to, pursuit of administrative remedies.

§80.130.Delivery of Warranty.

(a) The written warranty that the used manufactured home is habitable as per §1201.455 of the Standards Act, shall have been timely delivered if given to the homeowner at or prior to possession by the consumer or availability for possession [ the time the contract for sale is signed ].

(b) - (c) (No change.)

§80.131.Correction Requirements.

(a) (No change.)

(b) Except as provided in subsection (a) of this section, manufacturers, retailers, and installers shall perform their obligations in accordance with their respective written warranty within a reasonable period of time. A reasonable period of time is deemed to be forty (40) calendar days following receipt of the consumer's written notification unless there is good cause requiring more time. The consumer's written notification must be given within [ received by the manufacturer, retailer, or installer within forty (40) calendar days following the end of ] the one (1) year warranty period for new homes and for used homes within sixty (60) calendar days after the date of the sale or such longer time as may be provided for in the terms and conditions of the warranty documents .

(c) (No change.)

§80.132.Procedures for Handling Consumer Complaints.

In order to comply with §1201.002 of the Standards Act, to provide for the protection of the citizens who purchase manufactured housing and to provide fair and effective consumer remedies, the following procedures will be followed:

(1) On initial written contact by a consumer, the department will attempt to verify if the consumer has a valid complaint that is subject to the department's authority. If the department determines that the department has jurisdiction:

(A) If the consumer has not previously notified the manufacturer, retailer or installer [ in writing ], the department will forward the [ instruct the consumer to provide ] written notification to the manufacturer, retailer, or installer and give the license holder a reasonable amount of time to make repairs.

(B) If the consumer has previously provided written notification to the manufacturer, retailer or installer of the need for warranty service or repairs, but believes such has not been completed in a satisfactory manner, the department shall mail a complaint form to the consumer with instructions to complete it and return it to the department. On receipt of the complaint form, the department will make a determination regarding whether or not to open a consumer complaint. If a consumer complaint is opened, the department shall forward copies of the complaint form to the manufacturer, retailer and/or installer, as appropriate[ , by certified mail, return receipt requested ]. The department shall also include in the certified mail the "Manufacturer's Response Form" or "Retailer's Response Form," as appropriate, which must be completed and returned to the department within ten (10) business [ working ] days. The department shall perform a home inspection, if required. If a home inspection is performed, the department will assign responsibilities for repair, and notify the manufacturer, retailer, installer, and consumer of their responsibilities to complete such warranty or service repair in accordance with §80.131(b) of this title (relating to Correction Requirements).

(2) The department shall make a consumer complaint home inspection if a consumer, manufacturer, or retailer requests such inspection.

(A) Consumer Request. The consumer may, at any time, request that the department perform a consumer complaint home inspection . A written complaint regarding failure to provide warranty work is deemed to be a request for a consumer complaint inspection. No written complaint form is required if a possible imminent safety hazard exists. [ if the consumer has not been provided proper warranty service. The department may require that the request be in writing on a form provided by the department. If the department has reason to believe that the consumer complaint is covered by a warranty of a license holder, the department shall conduct a home inspection. There is no fee for an inspection performed at the request of the consumer when the department determines that a home inspection is warranted. ]

(B) - (C) (No change.)

(D) Within ten (10) business [ working ] days following the consumer complaint home inspection, the department shall mail its written report and orders (includes amended reports and orders), if any, to the consumer, manufacturer, retailer, and installer by certified mail, return receipt requested.

(E) If the consumer refuses to allow admission for inspection or service, the department will close the complaint. Also, any party denied access will not be held responsible for repairs deemed to be their responsibility.

(3) - (4) (No change.)

(5) If service or repairs cannot be made within the specified time frame, the license holder shall notify the department in writing prior to the expiration of the specified time frame by certified mail. The notice shall list those items which have been, or will be, completed within the time frame and shall show good cause why the remainder of the service or repairs cannot be made within the specified time frame. The license holder shall request an extension for a specific time. If the department fails to respond in writing to the request within five (5) business [ working ] days of the date of receipt of the notice of request for extension, the extension has been granted.

(6) - (7) (No change.)

§80.133.Administration of Claims under the Manufactured Homeowners' Recovery Trust Fund.

(a) (No change.)

(b) Documentation of a claim by a Licensee who is deemed to be a "consumer" under §1201.358(d) of the Standards Act - When either a manufacturer or a retailer has their license revoked or goes out of business and the party that went out of business or had its license revoked has failed to perform required warranty work on a timely basis, the Director may direct a licensee that is still in business to perform the warranty work. A licensee so directed will be deemed to be a "consumer" under §1201.358(d) of the Standards Act and entitled to be reimbursed from the Fund for the costs of performing such re-assigned warranty work.

(1) The Director, before authorizing any party performing re-assigned warranty work to proceed, will require that an estimate be submitted, itemizing the hourly cost of labor required, the estimated time to complete the work, the itemized costs of any material, equipment, and supplies, and such additional out-of-pocket expenses as the licensee believes it will incur. Overhead costs may be included, not to exceed 20% of the cost of labor and materials. If the required estimate is not submitted and approved prior to the commencement of re-assigned warranty work, the party performing the work may not be reimbursed for that work until the Director has been provided with evidence establishing that the amount billed was justifiable in all respects. The estimate must be on the form prescribed by the department [ Department ], properly completed and executed.

(2) An order by the Director authorizing re-assigned warranty work to be performed will specify that:

(A) (No change.)

(B) the licensee should keep complete records, subject to audit by the department [ Department ] for three years;

(C) (No change.)

(D) the required evidence that the re-assigned warranty work was performed should be supplied to the department [ Department ] within ten (10) days of completion; and

(E) (No change.)

(3) - (4) (No change.)

(5) Claims made by a consumer who is not a licensee and documentation of Fund claims--when a consumer has a covered claim against a licensee and the licensee has not satisfied the claim, the department [ Department ] shall take appropriate steps to make sure that the claim is proper and that all reasonable steps to satisfy the claim have been exhausted. In that regard:

(A) The department [ Department ], working with the consumer, shall identify the specific section(s) of law or rule that gave rise to the damages;

(B) (No change.)

(c) Attorneys' fees are subject to reimbursement from the Fund, subject to certain limitations. Before reimbursing a consumer for attorneys' fees, the department [ Department ] shall review the fee statement(s), which must indicate the specific services performed, the amount of work required, and the hourly rate(s) charged. Fees not directly relating to efforts to recover the unsatisfied claims are not reimbursable.

(d) The department [ Department ] shall require reasonable proof of efforts to collect the damages for which reimbursement from the Fund is sought.

(e) The department [ Department ] may require the assignment of claims against licensees for any amounts for which payments are made from the Fund. The department [ Department ] may re-assign any and all such claims to any bonding company or other surety that reimburses the Fund for such payments.

(f) If there is no licensee that can be assigned responsibility for warranty work or corrective action, the department [ Department ] may enter into agreements with one or more licensees to perform such work after requesting bids from the qualified licensee(s) in the immediate area where the work is to be performed or if, because of the scope and nature of the work, there are no qualified local licensees, with such other licensees as may possess the resources and expertise to submit bids and perform the work. If the only acceptable remedy is the replacement of a home, the department [ Department ] may negotiate with qualified manufacturers to identify the lowest cost acceptable resolution.

(g) Notification of warranty work orders, inspections, and re-assigned warranty work

(1) When an inspection is to be conducted, other than an initial installation inspection, such as a follow-up installation inspection or a complaint inspection, the department [ Department ] shall notify each licensee that has been assigned responsibility for warranty items, provided that the licensee still holds an active license, by notifying the licensee, by regular mail to their address of record, as on file with department [ Department ]. If a party to be notified of an inspection is no longer licensed but has left a mailing address on file with the department [ Department ], such party shall be given notice of any such inspection by first class mail to that address.

(2) When warranty work orders are issued, they will be sent to each licensee to whom responsibility has been assigned. They shall be sent to the licensee by regular mail to their address of record, as on file with department [ Department ].

(3) If a licensee who has been assigned warranty responsibilities is no longer in business, the department [ Department ] will, in addition to notifying their surety, notify them of the time and place of the inspection. Such notification to the out-of-business licensee shall be sent to them at their latest business address of record on file with the department [ Department ]. Unless the out-of-business licensee advises the department [ Department ], in writing, on or before the date of the inspection or actually attends the inspection, the department [ Department ] will re-assign the warranty work, if any, arising from the findings of the inspection to the retailer or manufacturer who is not out-of-business. The party to whom the warranty work is re-assigned shall perform the warranty work and shall be a consumer, as provided for in §1201.358(d) of the Standards Act, entitled to be reimbursed from the Fund.

(4) - (5) (No change.)

(6) Once a payment is made from the Fund, the department [ Department ] shall file a claim under the bond of the party primarily responsible for the unsatisfied claim. In the case of re-assigned warranty work reimbursed by the Fund, the claim shall be against the bond of the party that is no longer in business or whose license has been revoked.

(7) (No change.)

§80.135.Manufactured Housing Auctions.

(a) Auction of Manufactured Housing to Texas Consumers.

(1) - (4) (No change.)

(5) A manufactured home that has been salvaged or is not habitable may not be sold, conveyed, or transferred to a consumer as a manufactured home for dwelling purposes. [ The seller must surrender the title and HUD label or Texas Seal, or a statement that there was no label or seal, to the department along with the required fee and an application to cancel the title to business use, before the home is auctioned. ]

(6) - (7) (No change.)

(b) (No change.)

This agency hereby certifies that the proposal has been reviewed by legal counsel and found to be within the agency's legal authority to adopt.

Filed with the Office of the Secretary of State on February 14, 2005.

TRD-200500652

Timothy K. Irvine

Executive Director, Manufactured Housing Division

Texas Department of Housing and Community Affairs

Earliest possible date of adoption: March 27, 2005

For further information, please call: (512) 475-2206


Subchapter F. CONSUMER NOTICE REQUIREMENTS

10 TAC §80.183

The amended section is proposed under the Texas Manufactured Housing Standards Act, Occupations Code, Subtitle C, Chapter 1201, §1201.052, which provides the Department with authority to amend, add, and repeal rules governing the Manufactured Housing Division of the Department and under Texas Government Code, Chapter 2306, §2306.603, which authorizes the director to adopt rules as necessary to administer and enforce the manufactured housing program through the Manufactured Housing Division.

No other statute, code, or article is affected by the proposed amendment.

§80.183.Three Day Right of Rescission.

(a) The first calendar day after the day on which the applicable contract is executed is the first day, and the three day right of rescission expires unless notice has been given prior to midnight on the third calendar day following the date of execution of the applicable contract.

(b) The three day right of rescission may not be waived.

(c) Although a licensee is not required to obtain a signed acknowledgment, a [ A ] licensee may rely on a signed acknowledgement from a consumer, executed after the right of rescission has expired, confirming that the right expired without being exercised.

This agency hereby certifies that the proposal has been reviewed by legal counsel and found to be within the agency's legal authority to adopt.

Filed with the Office of the Secretary of State on February 14, 2005.

TRD-200500653

Timothy K. Irvine

Executive Director, Manufactured Housing Division

Texas Department of Housing and Community Affairs

Earliest possible date of adoption: March 27, 2005

For further information, please call: (512) 475-2206


Subchapter G. STATEMENTS OF OWNERSHIP AND LOCATION

10 TAC §80.205

The amended section is proposed under the Texas Manufactured Housing Standards Act, Occupations Code, Subtitle C, Chapter 1201, §1201.052, which provides the Department with authority to amend, add, and repeal rules governing the Manufactured Housing Division of the Department and under Texas Government Code, Chapter 2306, §2306.603, which authorizes the director to adopt rules as necessary to administer and enforce the manufactured housing program through the Manufactured Housing Division.

No other statute, code, or article is affected by the proposed amendment.

§80.205. Inventory Finance Liens [ Lien Information ].

[ (a) Inventory Financing Liens.]

(a) [ (1) ] A lien and security interest on manufactured homes in the inventory of a retailer, as well as to any proceeds of the sale of those homes, is perfected by filing an inventory finance security form approved by the department and in compliance with these sections.

(b) [ (2) ] The creditor-lender financing the inventory and the retailer must execute a security agreement which expressly sets forth the rights and obligations of the two parties in the inventory finance arrangement.

(c) [ (3) ] The inventory finance security form shall contain the following:

(1) [ (A) ] signatures of both the retailer and the creditor-lender;

(2) [ (B) ] the name, sales location, address, and license number of the retailer; and

(3) [ (C) ] the name and address of the creditor-lender.

(d) [ (4) ] A separate form must be filed for each licensed sales location.

(e) [ (5) ] For manufactured homes for which no Statement of Ownership and Location or Document of Title has been issued, the filing of the inventory-finance security form perfects a security interest in all manufactured homes, whether then owned or thereafter acquired, as well as to any proceeds of the sale of those homes, provided that:

(1) [ (A) ] the home is financed by the creditor-lender;

(2) [ (B) ] the creditor-lender has advanced any funds for the home; or

(3) [ (C) ] the creditor-lender has incurred any obligation for the home.

(f) [ (6) ] This security interest attaches to a particular manufactured home only when the act described in either subsection (e)(1), (2), or (3) of this section [ paragraph (5)(A), (B), or (C) of this subsection ] would either:

(1) [ (A) ] enable the retailer to acquire the manufactured home;

(2) [ (B) ] pay the existing balance of a creditor-lender for funds secured by a security interest in the manufactured home;

(3) [ (C) ] in the event that the retailer and manufacturer are the same entity, pay funds to the manufacturer-retailer after completion of the manufacture of the manufactured home; or

(4) [ (D) ] in the event that the retailer has no debt owed against the inventory, enable the retailer to use the manufactured home as security for a new debt.

(g) [ (7) ] No provision in the security agreement between the parties to an inventory financing arrangement shall in any way modify, change, or supersede the requirements of this section for the perfection of security interests in manufactured homes in the inventory of a retailer.

[ (b) Release of Liens.]

[ (1) The lienholder of a lien recorded on a Statement of Ownership and Location shall deliver a properly executed release of lien form prescribed by the department to the owner of record within thirty (30) calendar days of the satisfaction of the debt or obligation secured by the lien.]

[ (2) The lien recorded on a Statement of Ownership and Location shall be released by the department upon receipt of a release of lien form properly executed by the lienholder of record, and a new Statement of Ownership and Location shall be issued.]

[ (c) Foreclosure or Repossession.]

[ (1) In the event of sale after either foreclosure or repossession of a manufactured home that is not real property, the department shall issue a new Statement of Ownership and Location upon receipt of a properly executed application containing the following information:]

[ (A) The description of the home along with an indication of whether the home is a foreclosure or repossession;]

[ (B) The name and address of the lienholder and name of the person authorized to sign for the lienholder;]

[ (C) An indication of whether the home was repossessed by judicial order or sequestration. A true copy of the order or bill of sale shall be attached; and ]

[ (D) A certification that:]

[ (i) the home will be sold from a licensed retailer’s location; or]

[ (ii) the seller is not required to be licensed under Subchapter C of the Standards Act.]

[ (2) In the event of foreclosure or repossession of a manufactured home that is not real property, the department will not issue a new Statement of Ownership and Location until receipt of release of lien.]

[ (d) Right of Survivorship: If two or more eligible persons are shown as purchasers or transferees, they may execute the right of survivorship election on an application for a Statement of Ownership and Location. Such election constitutes an agreement for the right of survivorship. If the survivorship election is taken, then the department will issue a new Statement of Ownership and Location to the surviving person(s) upon receipt of a copy of the death certificate of the deceased person(s), and a properly executed application for Statement of Ownership and Location, and the applicable fee.]

This agency hereby certifies that the proposal has been reviewed by legal counsel and found to be within the agency's legal authority to adopt.

Filed with the Office of the Secretary of State on February 14, 2005.

TRD-200500654

Timothy K. Irvine

Executive Director, Manufactured Housing Division

Texas Department of Housing and Community Affairs

Earliest possible date of adoption: March 27, 2005

For further information, please call: (512) 475-2206


Subchapter H. TABLES AND FIGURES

10 TAC §80.240

The new section is proposed under the Texas Manufactured Housing Standards Act, Occupations Code, Subtitle C, Chapter 1201, §1201.052, which provides the Department with authority to amend, add, and repeal rules governing the Manufactured Housing Division of the Department and under Texas Government Code, Chapter 2306, §2306.603, which authorizes the director to adopt rules as necessary to administer and enforce the manufactured housing program through the Manufactured Housing Division.

No other statute, code, or article is affected by the proposed new rule.

§80.240.Tables and Figures.

(a) Tables.

(1) Maximum Spacing for Diagonal Ties.

Figure: 10 TAC §80.240(a)(1)

(2) Minimum Number of Diagonal Ties.

Figure: 10 TAC §80.240(a)(2)

(3) Maximum Spacing for Diagonal Ties (Wind Zone II) per side of the Assembled Unit.

Figure: 10 TAC §80.240(a)(3)

(4) Bracket Installation--Maximum Centerline Wall Opening for Column Uplift Brackets.

Figure: 10 TAC §80.240(a)(4)

(5) Floor Connections--Wind Zone I and II.

Figure: 10 TAC §80.240(a)(5)

(6) Roof Connection--Fastener Type and Spacing.

Figure: 10 TAC §80.240(a)(6)

(7) Main Panel Box Feeder Conductor Sizes.

Figure: 10 TAC §80.240(a)(7)

(8) Footer Capacities.

Figure: 10 TAC §80.240(a)(8)

(9) Pier Loads without Perimeter Supports.

Figure: 10 TAC §80.240(a)(9)

(10) Pier Loads with Perimeter Supports.

Figure: 10 TAC §80.240(a)(10)

(11) Mating Line Column Loads.

Figure: 10 TAC §80.240(a)(11)

(12) Enforcement Matrix.

Figure: 10 TAC §80.240(a)(12)

(b) Figures.

(1) Counties Located in Wind Zone II.

Figure: 10 TAC §80.240(b)(1)

(2) Anchor Installation.

Figure: 10 TAC §80.240(b)(2)

(3) Placement of Stabilizing Plates.

Figure: 10 TAC §80.240(b)(3)

(4) Wind Zone I Installation (Single & Multi-Section).

Figure: 10 TAC §80.240(b)(4)

(5) Diagonal Strap Placement for Piers Exceeding 36 in. in Height.

Figure: 10 TAC §80.240(b)(5)

(6) Diagonal and Vertical Ties.

Figure: 10 TAC §80.240(b)(6)

(7) Typical Installation Details.

Figure: 10 TAC §80.240(b)(7)

(8) Anchor Span.

Figure: 10 TAC §80.240(b)(8)

(9) Typical Longitudinal Stabilizing Device.

Figure: 10 TAC §80.240(b)(9)

(10) Longitudinal Ties.

Figure: 10 TAC §80.240(b)(10)

(11) Mating Line Surfaces.

Figure: 10 TAC §80.240(b)(11)

(12) Floor Connections.

Figure: 10 TAC §80.240(b)(12)

(13) Endwall Connections.

Figure: 10 TAC §80.240(b)(13)

(14) Roof Connection.

Figure: 10 TAC §80.240(b)(14)

(15) Exterior Roof Close Up.

Figure: 10 TAC §80.240(b)(15)

(16) HVAC (Heat/Cooling) Duct Crossover.

Figure: 10 TAC §80.240(b)(16)

(17) Multi-Section Water Crossover Connections.

Figure: 10 TAC §80.240(b)(17) (.pdf)

(18) Drain, Waste and Vent Floor Piping System.

Figure: 10 TAC §80.240(b)(18)

(19) Chassis Bonding.

Figure: 10 TAC §80.240(b)(19)

(20) Electrical Crossover.

Figure: 10 TAC §80.240(b)(20)

(21) Fuel Gas Pipe Crossover Connections.

Figure: 10 TAC §80.240(b)(21)

(22) Footer Configurations.

Figure: 10 TAC §80.240(b)(22) (.pdf)

(23) Pier Design (Single and Multi-Section Stack).

Figure: 10 TAC §80.240(b)(23)

(24) Perimeter Pier Front & Side View.

Figure: 10 TAC §80.240(b)(24)

(25) Typical Multi-Section Pier Layout.

Figure: 10 TAC §80.240(b)(25)

(26) Typical Single Section Pier Layout.

Figure: 10 TAC §80.240(b)(26)

(27) Determining Column Load and Marriage Line Elevation.

Figure: 10 TAC §80.240(b)(27)

This agency hereby certifies that the proposal has been reviewed by legal counsel and found to be within the agency's legal authority to adopt.

Filed with the Office of the Secretary of State on February 14, 2005.

TRD-200500655

Timothy K. Irvine

Executive Director, Manufactured Housing Division

Texas Department of Housing and Community Affairs

Earliest possible date of adoption: March 27, 2005

For further information, please call: (512) 475-2206


Subchapter I. FORMS

10 TAC §80.260

The new section is proposed under the Texas Manufactured Housing Standards Act, Occupations Code, Subtitle C, Chapter 1201, §1201.052, which provides the Department with authority to amend, add, and repeal rules governing the Manufactured Housing Division of the Department and under Texas Government Code, Chapter 2306, §2306.603, which authorizes the director to adopt rules as necessary to administer and enforce the manufactured housing program through the Manufactured Housing Division.

No other statute, code, or article is affected by the proposed new rule.

§80.260.Required and Optional Forms.

(a) Required Forms. Any alternative form or any modification of any of the following forms may be accepted by the department if the director determines that all information necessary to the administration of the Standards Act has been provided and that in all other respects the alternative form or modified form is acceptable AND the director has evidenced such approval in writing prior to the acceptance of any such alternative or modified form. The director may require a legal opinion from counsel for the person seeking to use an alternative or modified form that it complies with the Standards Act and addressing such other legal issues as the director may determine. The director may place limitations or conditions on the approval of any alternative or modified form.

(1) Site Preparation Notice.

Figure: 10 TAC §80.260(a)(1)

(2) Consumer Disclosure Statement.

Figure: 10 TAC §80.260(a)(2) (.pdf)

(3) 163 Disclosure--Choosing a Loan to Buy a Manufactured Home.

Figure: 10 TAC §80.260(a)(3) (.pdf)

(4) Notice of Installation (Form T).

Figure: 10 TAC §80.260(a)(4) (.pdf)

(5) Estimate for Reassigned Warranty Work.

Figure: 10 TAC §80.260(a)(5) (.pdf)

(6) Application for Statement of Ownership and Location.

Figure: 10 TAC §80.260(a)(6) (.pdf)

(7) Release or Foreclosure of Lien (Form B).

Figure: 10 TAC §80.260(a)(7) (.pdf)

(8) Quick Processing Form.

Figure: 10 TAC §80.260(a)(8) (.pdf)

(9) Form M.

Figure: 10 TAC §80.260(a)(9) (.pdf)

(10) Affidavit of Fact for Right of Survivorship.

Figure: 10 TAC §80.260(a)(10) (.pdf)

(b) Optional Forms.

(1) Spanish Version of Consumer Disclosure Statement.

Figure: 10 TAC §80.260(b)(1) (.pdf)

(2) Spanish Version of 163 Disclosure--Choosing a Loan to Buy a Manufactured Home.

Figure: 10 TAC §80.260(b)(2) (.pdf)

This agency hereby certifies that the proposal has been reviewed by legal counsel and found to be within the agency's legal authority to adopt.

Filed with the Office of the Secretary of State on February 14, 2005.

TRD-200500656

Timothy K. Irvine

Executive Director, Manufactured Housing Division

Texas Department of Housing and Community Affairs

Earliest possible date of adoption: March 27, 2005

For further information, please call: (512) 475-2206


Chapter 80. MANUFACTURED HOUSING

The Manufactured Housing Division of the Texas Department of Housing and Community Affairs (Department) proposes repeal of §§80.50 - 80.52, 80.63, 80.129, 80.134, 80.136, 80.137, 80.181, 80.182, 80.200, 80.202 - 80.204, and 80.206 - 80.209. The repeals are necessary to remove unnecessary text, move text to more appropriate sections, or to propose a new rule to replace the repeal.

Section 80.50 - the rule is not necessary since the Wind Zone regulations are stated in the Standards Act.

Section 80.51 - relocated to various sections in proposed revisions to §80.53 and §80.54.

Section 80.52 - clarifications are made in proposed revisions in §80.54 and the definition of Permanent Foundation that make this rule unnecessary. Also, the certification form is eliminated since it is not required that a home be on a permanent foundation to be treated as real property.

Section 80.63 - all matters are now appropriately addressed in §80.54 and §80.62.

Section 80.129 - proposing a new §80.129 and moving the previous text to §80.127 (Sanctions and Penalties) and the Enforcement Matrix to new Subchapter H (Tables and Figures).

Figure: 10 TAC §80.129(g) - Moved Enforcement Matrix to new §80.240(a)(12).

Section 80.134 - relocated portions of the text to §80.121 (Retailer's Responsibilities) and deleted text that is no longer necessary.

Section 80.136 - supporting documentation relating to permanent foundations is no longer required and the closing requirements are clearly set forth in the statute.

Section 80.137 - relocated subsection (b) and forms to new Subchapter I (Forms).

Figure: 10 TAC §80.137(a)(1) - Moved Notice of Installation (Form T) to new §80.260(a)(4).

Figure: 10 TAC §80.137(a)(2) -The Down Payment Verification Affidavit is deleted.

Figure: 10 TAC §80.137(a)(3) - Moved Estimate for Reassigned Warranty Work form to new §80.260(a)(5).

Section 80.181 - relocated necessary text to §80.121(e) and forms to new Subchapter I (Forms).

Figure: 10 TAC §80.181(1) - Moved the Consumer Disclosure Statement form to new §80.260(a)(2).

Figure: 10 TAC §80.181(2) - Moved the Spanish version of the Consumer Disclosure Statement form to new §80.260(b)(1).

Section 80.182 - relocated necessary text to §80.121(f) and forms to new Subchapter I (Forms).

Figure: 10 TAC §80.182(1) - Moved the 163 Disclosure form to new §80.260(a)(3).

Figure: 10 TAC §80.182(2) - Moved the Spanish version of the 163 Disclosure form to new §80.260(b)(2).

Section 80.200 - deleted subsection (a) and relocated (b) to §80.121(a)(1)(L) (Retailer's Responsibilities).

Section 80.202 - relocated fees to §80.20(j).

Section 80.203 - relocated to §80.120 (Manufacturer's Responsibilities).

Section 80.204 - the Notice of Installation (Form T) is no longer filed with the Application for Statement of Ownership and Location.

Section 80.206 - the rule is no longer necessary.

Section 80.207 - a habitability inspection is no longer required for changes in election from real to personal property, and habitability inspection requirements for converting business use and salvage homes to residential use are already set forth in §80.201.

Section 80.208 - the rule is no longer necessary.

Section 80.209 - relocated forms to new Subchapter I (Forms).

Figure: 10 TAC §80.209(a) - Moved the Application for Statement of Ownership and Location form to new §80.260(a)(6).

Figure: 10 TAC §80.209(b) - Moved the Release or Foreclosure of Lien form to new §80.260(a)(7).

Timothy K. Irvine, Executive Director of the Manufactured Housing Division of the Texas Department of Housing and Community Affairs, has determined that for the first five-year period the repeal is in effect, there will be no fiscal implications for state or local government as a result of enforcing or administering the repeal.

Mr. Irvine also has determined that for each year of the first five years the repeal is in effect the public benefit as a result of enforcing the repeal will be to eliminate unnecessary or redundant verbiage and to propose new rules and revisions that organize the rules by grouping in related subjects that are more logical. The repeal is expected to have no material economic costs to persons/businesses that are required to comply with the repeal as proposed. There are expected to be no fiscal implications for units of local government as a result of enforcing or administering the repeal.

Comments may be submitted to Mr. Timothy K. Irvine, Executive Director of the Manufactured Housing Division, of the Texas Department of Housing and Community Affairs, P. O. Box 12489, Austin, Texas 78711-2489 or by e-mail at the following address tirvine@tdhca.state.tx.us. The deadline for comments is 30 days after publication in the Texas Register .

Subchapter D. STANDARDS AND REQUIREMENTS

(Editor's note: The text of the following sections proposed for repeal will not be published. The sections may be examined in the offices of the Texas Department of Housing and Community Affairs or in the Texas Register office, Room 245, James Earl Rudder Building, 1019 Brazos Street, Austin.)

10 TAC §§80.50 - 80.52, 80.63

The repeal is proposed under the Texas Manufactured Housing Standards Act, Occupations Code, Subtitle C, Chapter 1201.052, which provides the Department with authority to amend, add, and repeal rules governing the Manufactured Housing Division of the Department and under Texas Government Code, Chapter 2306, §2306.603, which authorizes the director to adopt rules as necessary to administer and enforce the manufactured housing program through the Manufactured Housing Division.

No other statute, code, or article is affected by the repealed rules.

§80.50.Wind Zone Regulations.

§80.51.Manufactured Home Installation Requirements.

§80.52.Permanent Foundation Criteria.

§80.63.Other Materials and Methods for Manufactured Homes.

This agency hereby certifies that the proposal has been reviewed by legal counsel and found to be within the agency's legal authority to adopt.

Filed with the Office of the Secretary of State on February 14, 2005.

TRD-200500643

Timothy K. Irvine

Executive Director, Manufactured Housing Division

Texas Department of Housing and Community Affairs

Earliest possible date of adoption: March 27, 2005

For further information, please call: (512) 475-2206


Subchapter E. GENERAL REQUIREMENTS

(Editor's note: The text of the following sections proposed for repeal will not be published. The sections may be examined in the offices of the Texas Department of Housing and Community Affairs or in the Texas Register office, Room 245, James Earl Rudder Building, 1019 Brazos Street, Austin.)

10 TAC §§80.129, 80.134, 80.136, 80.137

The repeal is proposed under the Texas Manufactured Housing Standards Act, Occupations Code, Subtitle C, Chapter 1201.052, which provides the Department with authority to amend, add, and repeal rules governing the Manufactured Housing Division of the Department and under Texas Government Code, Chapter 2306, §2306.603, which authorizes the director to adopt rules as necessary to administer and enforce the manufactured housing program through the Manufactured Housing Division.

No other statute, code, or article is affected by the repealed rules.

§80.129.Determinations Regarding the Pursuit of Administrative Penalties and Enforcement Actions.

§80.134.Deceptive Practices.

§80.136.Homes Acquired on or after January 1, 2002.

§80.137.Required Forms.

This agency hereby certifies that the proposal has been reviewed by legal counsel and found to be within the agency's legal authority to adopt.

Filed with the Office of the Secretary of State on February 14, 2005.

TRD-200500644

Timothy K. Irvine

Executive Director, Manufactured Housing Division

Texas Department of Housing and Community Affairs

Earliest possible date of adoption: March 27, 2005

For further information, please call: (512) 475-2206


Subchapter F. CONSUMER NOTICE REQUIREMENTS

10 TAC §80.181, §80.182

(Editor's note: The text of the following sections proposed for repeal will not be published. The sections may be examined in the offices of the Texas Department of Housing and Community Affairs or in the Texas Register office, Room 245, James Earl Rudder Building, 1019 Brazos Street, Austin.)

The repeal is proposed under the Texas Manufactured Housing Standards Act, Occupations Code, Subtitle C, Chapter 1201.052, which provides the Department with authority to amend, add, and repeal rules governing the Manufactured Housing Division of the Department and under Texas Government Code, Chapter 2306, §2306.603, which authorizes the director to adopt rules as necessary to administer and enforce the manufactured housing program through the Manufactured Housing Division.

No other statute, code, or article is affected by the repealed rules.

§80.181.Section 162 Notice.

§80.182.163 Disclosure.

This agency hereby certifies that the proposal has been reviewed by legal counsel and found to be within the agency's legal authority to adopt.

Filed with the Office of the Secretary of State on February 14, 2005.

TRD-200500645

Timothy K. Irvine

Executive Director, Manufactured Housing Division

Texas Department of Housing and Community Affairs

Earliest possible date of adoption: March 27, 2005

For further information, please call: (512) 475-2206


Subchapter G. STATEMENTS OF OWNERSHIP AND LOCATION

(Editor's note: The text of the following sections proposed for repeal will not be published. The sections may be examined in the offices of the Texas Department of Housing and Community Affairs or in the Texas Register office, Room 245, James Earl Rudder Building, 1019 Brazos Street, Austin.)

10 TAC §§80.200, 80.202 - 80.204, 80.206 - 80.209

The repeal is proposed under the Texas Manufactured Housing Standards Act, Occupations Code, Subtitle C, Chapter 1201.052, which provides the Department with authority to amend, add, and repeal rules governing the Manufactured Housing Division of the Department and under Texas Government Code, Chapter 2306, §2306.603, which authorizes the director to adopt rules as necessary to administer and enforce the manufactured housing program through the Manufactured Housing Division.

No other statute, code, or article is affected by the repealed rules.

§80.200.Responsibility for Completion and Filing of an Application for a Statement of Ownership and Location.

§80.202.Fees for Title Documents.

§80.203.Manufacturer's Monthly Shipment Report.

§80.204.Installation Information.

§80.206.Assignment of Lien.

§80.207.Reinstatement of Canceled Documents of Title.

§80.208.Recording Tax Lien on Manufactured Homes.

§80.209.Statement of Ownership and Location Forms.

This agency hereby certifies that the proposal has been reviewed by legal counsel and found to be within the agency's legal authority to adopt.

Filed with the Office of the Secretary of State on February 14, 2005.

TRD-200500646

Timothy K. Irvine

Executive Director, Manufactured Housing Division

Texas Department of Housing and Community Affairs

Earliest possible date of adoption: March 27, 2005

For further information, please call: (512) 475-2206